9-40
IM 05P02C41-01EN
9.8.6 Segment switching (the controller switches to a remote setpoint when
the segment is completed after release) (JC=W.SR1 to W.SR5)
Description
The stand-by action is performed in the last segment of program operation and the state
becomes the remote operation state after the stand-by state is released. However, the
controller is in local-mode when burnout occurs.
The wait operation works.
Remote operation starts after
releasing wait action.
Setpoint
Time
Program pattern operation stop
Remote operation
Local target
setpoint (LSP)
(for control)
Program pattern
for control
Last segment
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu
symbol
JC
Junction code
STD
CONT: Switching for continuation
HOLD: Hold-on switching (the controller holds the
end-of-segment setpoint when the segment is
completed, to perform control).
LOC: Local-mode switching (the controller switches to
a local setpoint when the segment is completed).
REM: Remote-mode switching (the controller
switches to a remote setpoint when the segment
is completed).
W.SW1 to W.SW5: Wait during switching between
segments.
W.IV1 to W.IV5: Wait within a segment interval
.
W.SL1 to W.SL5: Segment switching (the controller
switches to a local setpoint when the segment is
completed after release.) (5 groups)
W.SR1 to W.SR5: Segment switching (the controller
switches to a remote setpoint when the segment
is completed after release.) (5 groups)
PLK.1 to PLK.30 (PLK.99): Linked to patterns 1 to 30 (99).
INS.: Allows a segment to be added to the end of a
specified segment.
DEL.: Allows a specified segment to be deleted.
PROG
WT.SW1 to
WT.SW5
Wait function
ON/OFF 1 to 5
STD
OFF: Disable
ON: Enable
WT.UP1 to
WT.UP5
Upper-side wait
zone 1 to 5
STD
0.0 to 10.0% of PV input range (EU)
WT.LO1 to
WT.LO5
Lower-side wait
zone 1 to 5
STD
WT.TM1 to
WT.TM5
Wait time 1 to 5
STD
OFF: No function
0.00 to 999.59 (“hour.minute” or “minute.
second”)
* Available only for the wait time at the
segment switching.
* Use the parameter TMU to set the time unit.
(Common in the instrument.)
TMU
Program time
unit
EASY HH.MM: hour.minute
MM.SS: minute.second
CTL
9.8 Setting the Operation in Segment Switching
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...