8.4.3 Switching PID According to SP
Description
The zone PID selection by SP switches between the groups of PID parameters according
to the SP. The maximum number of PID groups to be switched is 8. (Set RP1 to RP7)
The figure below shows the example of switching the group of PID parameters according
to the SP. It shows an example of dividing the PV input range from the maximum value to
the minimum value into five zones by reference points 1 to 4. (Set RP1 to RP4.)
Maximum value of
PV input range
Minimum value of
PV input range
Reference point 4
(PID of group 5)
(PID of group 4)
(PID of group 3)
(PID of group 2)
PID of group 2
SP
SP
PID of group 3
(PID of group1)
Time
PID of group 1
PID of group 3
PID of grop 2
PID of group 5
Reference point 3
Reference point 2
Reference point 1
PID No. to be selected
PID of group 4
The PV input range can be divided into the number of zones that is set in the reference
point.
Reference deviation can be set at the same time.
►
Reference deviation: 8.4.5 Switching PID according to Deviation (Reference Deviation)
8.4 Switching PID
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...