4-14
IM 05P07A01-01EN
4.4.4 Response Error Codes
When a response is returned to a request:
When the PDU in the request contains an inconsistency, the UT75A/UT55A/UT35A/
UP55A/UP35A does not perform any processing, and returns the following request.
Element
MBAP Header
PDU
Number of bytes
2
2
2
1
1
1
Command
element
Transfer ID
Protocol ID Number of
bytes
Unit ID
Function
code*
Error Code
(Hex)
Optional value
0000
03
01
* The value of “function code (Hex) + 80 (Hex)” is set in the function code.
Response error codes
Error Code
Meaning
Cause
01
Function code error
The function code does not exist.
02
D register/I relay No. error
A No. outside the range has been specified.
03
Number of D registers/
I relays error
A number of registers/relays outside the range has been specified.
09
Monitor not specified
An attempt was made to read a monitor without specifying the monitor.
When a response is not returned to a request
In the following instances, the UT75A/UT55A/UT35A/UP55A/UP35A does not perform
any processing and does not return a response:
• When a connection has not been established on the TPC/IP socket interface
• When the MBAP Header in a request contains an inconsistency
* As a measure for the above, execute time-out processing by the communication function or
communication program on the host computer.
4.4 Communication with Host Computer
Summary of Contents for UTAdvanced Series
Page 17: ...Blank Page...
Page 77: ...Blank Page...
Page 285: ...Blank Page...
Page 325: ...Blank Page...
Page 467: ...Blank Page...
Page 557: ...Blank Page...
Page 825: ...Blank Page...
Page 861: ...Blank Page...
Page 863: ...Blank Page...
Page 865: ...Blank Page...