13-19
IM 05P07A01-01EN
Functions and
Applications of I Relays (for UT35A-L)
13
13.4 Reading via Communication
When reading the alarm status
Read I relay numbers 4321 to 4336 for alarm-1 to alarm-3 status.
I relay No.
Symbol
Event
4321 to 4336
ALM1_L1~ALM3_L1
Alarm-1 to alarm-3 status (Same as D2011) *
•
•
•
•
•
•
4545 to 4576
*: The contents of alarm-1 to alarm-4 status (I relay numbers 4321 to 4336: ALM1_L1 to
ALM4_L1) are the same as the bit configuration of D register number D2011 (alarm-1
to alarm-4 status). Refer to the bit configuration of D2011 described in “Chapter 12
Functions and Applications of D Registers (for UT35A).”
The following shows the bit configuration of D2011 described in “Chapter 12 Functions
and Applications of D Registers (for UT35A-L).”
Bit Configuration of D2011: ALM_L1 (Alarm-1 to alarm-4 status)
Bit
Symbol
Event
0
ALM1_L1
‘1’ when alarm 1 is ON; ‘0’ when OFF
1
ALM2_L1
‘1’ when alarm 2 is ON; ‘0’ when OFF
2
ALM3_L1
‘1’ when alarm 3 is ON; ‘0’ when OFF
3
4
5 to 15
Note
When specifying an I relay number for communication, begin the number with the character “I.”
Example: Set “I4321” to specify the ALM1_L1 (I relay No.: 4321).