12-52
IM 05P07A01-01EN
12.5 UT35A-L D Registers
12.5.10 D Registers Differring in Content from GREEN Series
D0915 to D0917: Alarm-1 type to alarm-3 type
UTAdvanced
Register
No.
Description
Range and meaning of value
D0915
AL1.T_L1
Alarm-1 type
0: Disable
01: PV high limit
02: PV low limit
05: Deviation high limit
06: Deviation low limit
07: Deviation high and low limits
08: Deviation within high and low limits
29: PV velocity
30: Fault diagnosis
31: FAIL
D0916
AL2.T_L1
Alarm-2 type
D0917
AL3.T_L1
Alarm-3 type
GREEN Series
Register
No.
Description
Range and meaning of value
D0915
AL1
Alarm-1 type
OFF (0)
1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
3: Deviation high limit (energized, no stand-by action)
4: Deviation low limit (energized, no stand-by action)
5: Deviation high limit (de-energized, no stand-by action)
6: Deviation low limit (de-energized, no stand-by action)
For other alarm types, see “Changing Alarm Type” of GREEN series (UT350L)
User
’
s manual.
D0916
AL2
Alarm-2 type