13-6
IM 05P01D31-01EN
13.1.4 Changing Event Display
Description
The UT35A/UT32A has four event (EV) lamps.
The alarms 1 to 4 are assigned to EV1 to EV4.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu
symbol
EV1 to
EV4
EV1 to EV4
display
condition
registration
PRO
Setting range: 4001 to 6304
OFF: Disable
4321: Link to alarm 1 (Lit when the alarm occurs)
4322: Link to alarm 2 (Lit when the alarm occurs)
4323: Link to alarm 3 (Lit when the alarm occurs)
4325: Link to alarm 4 (Lit when the alarm occurs)
4529: Heater break alarm 1 (Lit when the alarm occurs)
4530: Heater break alarm 2 (Lit when the alarm occurs)
5025 to 5026: Link to DI1-DI2 (Lit when the
contact is closed)
5041 to 5045: Link to DI11-DI15 (E1-terminal
area) (Lit when the contact is closed)
5153 to 5155: Link to AL1-AL3 (Lit when the
contact is closed)
5169 to 5173: Link to DO11-DO12 (E1-terminal
area) (Lit when the contact is closed)
5217 to 5221: Link to DO41-DO45 (E4-terminal
area) (Lit when the contact is closed)
For other functions, see the UTAdvanced
Series Communication Interface User’s
Manual.
DISP
13.1 Setting Display Functions