11-17
IM 05P01D31-01EN
Alarm
Functions
11
11.6 Setting Alarm Action According to Operation
Mode
Description
The alarm action usually functions regardless of operation modes.
Setting the alarm mode allows the alarm action to be disabled in STOP or in STOP or
MAN mode.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
AMD
Alarm mode
STD
0: Always active
1: Not active in STOP mode
2: Not active in STOP or MAN
mode