2.3
Changing PV Input Type
The following operating procedure describes an example of changing the setting of K-type
thermocouple (-199.9 to 500.0
⬚
C) to RTD Pt100 (-199.9 to 500.0
⬚
C) and a measurement
range of 0.0 to 200.0
⬚
C.
PV input terminal
Thermocouple/mV/V input..............................
RTD input ..................................................
-
-
13
12
11
-
13
12
1.
Bring the operating display into view
(display appears at power on).
P V
AL1
2
3
4
S E T / E N T
Displays PV.
2.
Press the
S E T / E N T
key for more than 3 sec-
onds to call up the menu “OP.PA”.
P V
AL1
2
3
4
S E T / E N T
Displays
menu “OP.PA”.
3.
Press the
key once to display the
menu “STUP”.
P V
AL1
2
3
4
S E T / E N T
Displays
menu “STUP”.
4.
Press the
S E T / E N T
key once to display the
parameter “PWD”.
P V
AL1
2
3
4
S E T / E N T
Displays
parameter
“PWD”.
5.
Press the
S E T / E N T
key once to display the
menu “FUNC”.
P V
AL1
2
3
4
S E T / E N T
Displays
menu “FUNC”.
6.
Press the
key once to display the
menu “I/O”.
P V
AL1
2
3
4
S E T / E N T
Displays
menu “I/O”.
7.
Press the
S E T / E N T
key once to display the
parameter “IN” (PV input type).
P V
AL1
2
3
4
S E T / E N T
Displays
parameter
“IN”.
8.
Press the
or
key to display the
required setpoint. The figure below shows
an example of changing to RTD Pt100
(-199.9 to 500.0
⬚
C).
P V
AL1
2
3
4
S E T / E N T
Blinks during
change.