4-5
IM 04P03B01-01E
Setup Operations for Changing/Adding Functions (Basic Setting Mode)
4
4.4
Setting the RJC Function on TC Input
Channels
The RJC mode can be set on TC input channels. Basic Setting mode cannot be entered
when recording is in progress.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the
and
keys simultaneously for 3 seconds to display the
Basic Setting mode screen.
3.
Carry out the procedure shown in the figure below.
Press the
or
key to select the value.
For the procedure on how to enter values or characters, see page 19 in the
Operation Guide
.
To change the polarity, press the
or
key when the leftmost digit of the
value is blinking.
If you press the
key, the operation is cancelled, and the display returns to a
higher level menu.
Select the RJC mode of the
thermocouple input.
Select the channel number.
(When external (EXT) is selected)
Set the compensation voltage when
using the external RJC function.
Selects “RJC.”
(RJC)
(CH1)
(INT)
Channel number
The settings are activated.
(OK)
4.
Press the
key to set other channels.
If you are done, press the
key.
5.
To return to the Operation mode,
1. Press the
key, use the
or
key to select
, and press the
key.
2. Press the
or
key to select
or
, and press the
key.
Explanation
RJC
Sets the RJC mode.
Internal (
): Uses the RJC function of the recorder.
External (
): Uses an external RJC function. If external is selected, set the
compensation voltage.
Compensation Voltage
Sets the compensation voltage when using an external RJC function.
The compensation voltage can be set in the range of –19999
µ
V to 20000
µ
V.