Output
The GM can output relay signals (digital output module or digital input/output module) when an
alarm occurs, when a failure occurs, when they are manually turned on, or according to the event
action function.
The output (DO channel) can also be recorded.
Digital output module
Module
Model
Output type
Number of Channels
Digital output
GX90YD
Relay, SPDT(NO-C-NC)
6
Digital input/output
GX90WD
Relay, SPDT(NO-C-NC)
6
l
Alarm output
When an alarm assigned to a measurement channel occurs, a relay signal is output from the DO
channel that the alarm output is assigned to.
Alarm
occurrence
Relay output
l
Manual output
DO channels can be turned on and off through manual operation on the digital display screen
shown in the Web browser.
To use manual output, the following settings are required.
• Set the DO channel type to Manual.
• In Display settings, set Value Modification from the Monitor to On.
Relay on/off
l
Event action
A relay signal is output when an event occurs.
For the events that can use relay output, see section “3.2.2 Event Action Function” on page 3-18.
Event
occurrence
Relay output
3
Functions