4. START OF OPERATION
4-1
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020 -00
4.1 Integration of GSD
PROFIBUS PA system requires GSD file which describes the device parameters such as the transmission
rate supported, input, output data, data format and data length.
The GSD files described below are available to RAMC.
You can download the GSD file from
http://www.profibus.com/products/gsd-files/
Table 4.1 GSD files
GSD file name
Ident. Number
Comment
PA139700.GSD (AIx1)
0x9700
Profile specific
RY014582.GSD
0x4582
Device specific
4.2 Important Device Settings
The tables below show items (parameters) which need special care to ensures a proper working of the
RAMC Profibus type.
Table 4.1 General settings
Item
Settings
Bus address
Set to 0x7E (126) by default unless otherwise specified when ordered
In case of unit change (compared to initial ordering) it is recommended to change the OUT_SCALE parameter
as described in table 4.3 only. Change of the Process Variable needs in addition the changes described in
the tables 4.2 and 4.3.
Table 4.2 Initial settings of Transducer Block
Item
Settings for Volume flow
Settings for Mass flow
Parameter: VOLUME_FLOW_UNITS
Choose unit (initially set to unit specified
when ordered)
Not active 1("Volume flow passivated")
Parameter: MASS_FLOW_UNITS
Not active 1 ("Mass flow passivated")
Choose unit (initially set to unit specified
when ordered)
NOTE
Change of the parameters VOLUME_FLOW_UNITS to MASS_FLOW_UNITS or vice versa needs in
addition the adaptation of the parameter CHANNEL inside the AI block, to make the change effective on
the OUT parameter.
Table 4.3 Initial settings of AI Function Block
Item
Settings for Volume flow
Settings for Mass flow
Parameter: PV_SCALE
Sub-parameter: Array 1
Set upper range limit (set to scale upper range as specified when ordered)
Parameter: PV_SCALE
Sub-parameter: Array 2
Set lower range limit (set to scale lower range as specified when ordered)
Parameter: OUT_SCALE
Sub-parameter: Units_Index
Choose unit (set to unit specified when ordered)
Parameter: OUT_SCALE
Sub-parameter: EU_at_100%
Set upper range limit (set to scale upper range as specified when ordered)
Parameter: OUT_SCALE
Sub-parameter: EU_at_0%
Set lower range limit (set to scale lower range as specified when ordered)
Parameter: CHANNEL
0x0111 (273)
0x0115 (277)
4. Start of Operation