<2. Initial Settings>
2-7
IM 05D01C12-41E
4th Edition: May 31, 2006-00
2.3
Changing PV Input Type
The following operating procedure describes an example of changing the setting of K-type
thermocouple (-200.0 to 500.0
C) to RTD Pt100 (-200.0 to 500.0
C) and a measurement
range of 0.0 to 200.0
C.
PV input terminal
Thermocouple/mV/V input..............................
RTD input ..................................................
-
-
13
12
11
-
13
12
1.
Bring the operating display into view
(display appears at power on).
P V
AL1
2
3
4
MAN
REM
S E T / E N T
A/M
Displays
target setpoint-1
“1.SP”.
Displays PV.
2.
Press the
S E T / E N T
key for more than 3
seconds to call up the menu “OP.PA”.
P V
AL1
2
3
4
MAN
REM
SET/ENT
A/M
Displays
symbol “D-U”.
Displays
menu “OP.PA”.
3.
Press the
key once to display the
menu “STUP”.
PV
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
menu “STUP”.
4.
Press the
S E T / E N T
key once to display the
menu “SP”.
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays
menu “SP”.
5.
Press the
key six times to display the
menu “I/O”.
P V
AL1
2
3
4
MAN
REM
SET/ENT
A/M
Displays
menu “I/O”.
6.
Press the
S E T / E N T
key once to display the
parameter “IN” (PV input type).
P V
AL1
2
3
4
MAN
REM
SET/ENT
A/M
Displays
parameter
“IN”.
7.
Press the
or
key to display the
required setpoint. The figure below shows
an example of changing to RTD Pt100
(-200.0 to 500.0
C).
PV
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Blinks during
change.
8.
Press the
S E T / E N T
key once to register the
setpoint.
P V
A L 1
2
3
4
M A N
R E M
SET/ENT
A / M