background image

User’s

Manual

1

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan

Phone: +81-422-52-7179  Facsimile: +81-422-52-6793

http://www.yokogawa.com/ns/juxta/im/

You can download the latest manuals from the following website:

Please read through this User’s Manual before use for correct handling.

Please keep this User’s Manual for future reference.

IM 77J01R06-01E

7th Edition Aug. 2020 (YK)

CAUTIONARY NOTES FOR SAFE USE OF 

THE PRODUCT

This User’s Manual should be carefully read before installing and 

operating the product. Please keep this User’s Manual for future 

reference.

For more information of the safety precautions, please refer to the 

“Precautions on the Use of the JUXTA Series (IM 77J01A00-91Z1)”.

The related manuals and general specifications are shown in the 

table below.

Doc. Name

Doc. Number 

Precautions on the Use of the JUXTA Series (User’s Manual) IM 77J01A00-91Z1

Model VJR6 RTD Converter (User’s Manual)

IM 77J01R06-01E

(This manual)

Model VJR6 RTD Converter  

(General Specifications)

GS 77J01R06-01E

User’s manuals in the above table are essential parts of the 

product; keep it in a safe place for future reference.

This manual is intended for the following personnel;   

 •

Engineers responsible for installation, wiring, and maintenance 

of the equipment.

 • Personnel responsible for normal daily operation of the 

equipment.

The following symbol is used on the product and in this manual to 

ensure safe usage.

 WARNING

Calls attention to actions or conditions that could 

cause serious or fatal injury to the user, and indicates 

precautions that should be taken to prevent such 

occurrences.

 CAUTION

Calls attention to actions or conditions that could 

cause injury to the user or damage to the instrument 

or property and indicates precautions that should be 

taken to prevent such occurrences.

CHECKING PRODUCT SPECIFICATIONS 

AND PACKAGE

(1) Checking the Model and Product Specifications

  Check that the model and specifications indicated on the 

nameplate attached to the main unit are as ordered.

(2) Packaged Items

  Check that the package contains the following items:

 •

VJR6: 1 unit

 

Standard Accessories: 

 •

Tag number label: 1 sheet

 •

User’s manual (IM 77J01R06-01E, this manual): 1 copy

 •

User’s manual (IM 77J01A00-91Z1): 1 copy

GENERAL

This plug-in type RTD converter is connected to an IEC/JIS-

standard resistance temperature detector (RTD) to convert 

temperature signals into isolated DC current or DC voltage 

signals.

MODE AND SUFFIX CODES

Model

Suffix Codes

Description

VJR6

-0

x x -x x x x /x

RTD Converter

Fixed code

-0

Always -0

Output

1

1 output

2

2 outputs

Power supply

6

100-240 V AC/DC 

(*1)

7

15-30 V DC 

(*2)

Input signal

-1

Pt100 (ITS-90)

-2

JPt100 (JIS'89)

-3

Pt50 (JIS'81)

-4

Pt100 (IPTS-68)

-Z

Custom order

Output-1

A

4 to 20 mA DC

B

2 to 10mA DC

C

1 to 5 mA DC

D

0 to 20 mA DC

E

0 to 16 mA DC

F

0 to 10 mA DC

G

0 to 1 mA DC

1

0 to 10 mV DC

2

0 to 100 mV DC

3

0 to 1 V DC

4

0 to 10 V DC

5

0 to 5 V DC

6

1 to 5 V DC

7

-10 to +10 V DC

Z

Custom order 

*3

Output-2

A

4 to 20mA DC

6

1 to 5V DC

N

No output-2

Z

Custom order 

*3

Burnout

U

UP

D

DOWN

N

OFF

Option

/SN

No socket (with socket if not 

specified)

/C0

Coating 

*4

/FB

Fuse bypass 

*4

/DF

Fahrenheit unit

*1

Operating range: 85-264 V

*2

Operating range: 12-36 V

*3 DC voltage signal or DC current signal

*4

When option code /C0 or /FB is specified, the conformity to the safety 

and EMC standards is excluded. CE marking is not applicable.

Model VJR6

RTD Converter

(Isolated Single-output and Isolated Dual-

output Types)

Reviews: