background image

User’s

Manual

1

Thank you for purchasing the JUXTA Signal Conditioner.

Please read through this manual before use for correct handling.

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan

Phone: +81-422-52-7179  Facsimile: +81-422-52-6793

http://www.yokogawa.com/ns/juxta/im/

You can download the latest manuals from the following website:

IM 77J01P08-01E

6th Edition July 2023 (YK)

CAUTIONARY NOTES FOR SAFE USE OF THE 

PRODUCT

This User’s Manual should be carefully read before installing 

and operating the product. Please keep this User’s Manual for 

future reference.For more information of the safety precautions, 

please refer to the “Precautions on the Use of the JUXTA 

Series (IM 77J01A00-91Z1)”. The related manuals and general 

specifications are shown in the table below.

Doc. Name

Doc. Number 

Precautions on the Use of the JUXTA Series (User’s 

Manual)

IM 77J01A00-91Z1

Model VJP8 Pulse Rate Converter (User’s Manual) IM 77J01P08-01E

(This manual)

Model VJP8 Pulse Rate Converter (General Specifications)

GS 77J01P08-01E

User’s manuals in the above table are essential parts of the 

product; keep it in a safe place for future reference.

This manual is intended for the following personnel;   

 •

Engineers responsible for installation, wiring, and maintenance 

of the equipment.

 • Personnel responsible for normal daily operation of the 

equipment.

The following symbol is used on the product and in this manual to 

ensure safe usage.

 WARNING

Calls attention to actions or conditions that could 

cause serious or fatal injury to the user, and indicates 

precautions that should be taken to prevent such 

occurrences.

 CAUTION

Calls attention to actions or conditions that could 

cause injury to the user or damage to the instrument 

or property and indicates precautions that should be 

taken to prevent such occurrences.

QR Code

The product has a QR Code pasted for efficient plant 

maintenance work and asset information management.

It enables confirming the specifications of purchased products 

and user’s manuals.

For more details, please refer to the following URL.

https://www.yokogawa.com/qr-code

*  QR Code is a registered trademark of DENSO WAVE 

INCORPORATED.

CHECKING PRODUCT SPECIFICATIONS 

AND PACKAGE

(1) 

Checking the Model and Product Specifications

  Check that the model and specifications indicated on the 

nameplate attached to the main unit are as ordered.

(2)  Packaged Items

  Check that the package contains the following items:

 •

VJP8: 1 unit

  Standard Accessories:

 •

Tag number label: 1 sheet

 •

Range label: 1 sheet

 •

Socket (T9093FL): 1 piece 

 

(when /SN option is not specified.)

 •

Shunt resistor(E9786WL):1 piece  

 

(When optional code /R is specified)

 • User's Manual (

IM 77J01P08-01E,

this manual): 1 copy

 •

User’s manual (IM 77J01A00-91Z1): 1 copy

GENERAL

 • This compact plug-in type pulse rate converter receives pulse 

signals from the field and converts them into various isolated 

pulse outputs at a set pulse rate. It can also operate as a 

pulse repeater (input frequency = output frequency) by  setting 

the pulse rate and pulse width type.

MODEL AND SUFFIX CODES

Model

Suffix codes

Description

VJP8

-0

x x -x x x

0

/x

Pulse Rate Converter  

(Multi-function)

-0

Always -0

Output

1

1 output

2

2 outputs

Power supply

6

100-240 V AC/DC 

(*1)

7

15-30 V DC 

(*2)

Transmitter power 

supply

-1

12 V DC ±10%

-2

24 V DC ±10%

Output-1 signal

1

Open collector (30 V DC/200 mA)

3

Contactless AC switch 

(*3)

5

Voltage pulse (5 V ±10%)

6

Voltage pulse (12 V ±10%)

7

Voltage pulse (24 V ±10%)

Output-2 signal

1

Open collector (30 V DC/200 mA)

3

Contactless AC switch 

(*3)

5

Voltage pulse (5 V ±10%)

6

Voltage pulse (12 V ±10%)

7

Voltage pulse (24 V ±10%)

P

Communication function (RS-485)

N

No output-2

0

Always 0

Options

/SN

No socket (with socket if not 

specified)

/R

With 200 Ω shunt resistor

(Specify when current pulse input.)

/C0

Coating 

(*3)

/FB

Fuse bypass 

(*3)

*1

Operating range: 85 to 264 V AC/DC

*2

Operating range: 12 to 36 V DC

*3

When specifying contactless AC switch and suffix codes /C0 or /FB, 

CE marking is not applicable because the product does not conform to 

safety and EMC standards. 

Note: An exclusive User’s Manual might be attached to the 

products whose suffix codes or option codes contain the code 

“Z” (made to customers’ specifications). Please read it along 

with this manual.

Model VJP8

Pulse Rate Converter 

(Multi-function)

(Isolated Single-output and Isolated Dual-

output Types)