Model VJH1

Isolator

(Isolated Single-output and  

Isolated Dual-output Types)

CAUTIONARY NOTES FOR SAFE USE OF THE 

PRODUCT

This User’s Manual should be carefully read before installing and 

operating the product. Please keep this User’s Manual for future 

reference.

For more information of the safety precautions, please refer to the 

“Precautions on the Use of the JUXTA Series (IM 77J01A00-91Z1)”.

The related manuals and general specifications are shown in the 

table below.

Doc. Name

Doc. Number 

Precautions on the Use of the JUXTA Series (User’s Manual) IM 77J01A00-91Z1

Model VJH1 Isolator (User’s Manual)

IM 77J01H01-01E

(This manual)

Model VJH1 Isolator (General Specifications)

GS 77J01H01-01E

User’s manuals in the above table are essential parts of the 

product; keep it in a safe place for future reference.

This manual is intended for the following personnel;   

 •

Engineers responsible for installation, wiring, and maintenance 

of the equipment.

 • Personnel responsible for normal daily operation of the 

equipment.

The following symbol is used on the product and in this manual to 

ensure safe usage.

 WARNING

Calls attention to actions or conditions that could 

cause serious or fatal injury to the user, and indicates 

precautions that should be taken to prevent such 

occurrences.

 CAUTION

Calls attention to actions or conditions that could 

cause injury to the user or damage to the instrument 

or property and indicates precautions that should be 

taken to prevent such occurrences.

CHECKING PRODUCT SPECIFICATIONS 

AND PACKAGE

(1) Checking the Model and Product Specifications

  Check that the model and specifications indicated on the 

nameplate attached to the main unit are as ordered.

(2) Packaged Items

  Check that the package contains the following items:

 •

VJH1: 1 unit

 

Standard Accessories: 

 •

Tag number label: 1 sheet

 •

Shunt resistor (for current input *): 1 piece

*  Excluding option codes /C and /HC.

 •

User’s manual (IM 77J01H01-01E, this manual): 1 copy

 •

User’s manual (IM 77J01A00-91Z1): 1 copy

IM 77J01H01-01E

7th Edition Aug. 2020 (YK)

GENERAL

This plug-in type isolator converts DC current or DC voltage 

signals into isolated DC current or DC voltage signals.

 •

With OOP: VJH1/C (Option code /C)

  When the load circuit opens (OOP: output open), input 

resistance increases rapidly to 48kΩ or more so as to detect 

the open state through the input device.

 •

With OOP (HART communication): 

 

VJH1/HC (Option code /HC)

  In addition to the load circuit open (OOP) detection function, 

HART communication signals are relayed bidirectionally with 

the field device and host device isolated.

User’s

Manual

1

Thank you for purchasing the JUXTA Signal Conditioner.

Please read through this manual before use for correct handling.

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan

Phone: +81-422-52-7179  Facsimile: +81-422-52-6793

http://www.yokogawa.com/ns/juxta/im/

You can download the latest manuals from the following website:

Summary of Contents for JUXTA VJH1

Page 1: ...ause injury to the user or damage to the instrument or property and indicates precautions that should be taken to prevent such occurrences CHECKING PRODUCT SPECIFICATIONS AND PACKAGE 1 Checking the Model and Product Specifications Check that the model and specifications indicated on the nameplate attached to the main unit are as ordered 2 Packaged Items Check that the package contains the followin...

Page 2: ...1 Wall Mounting Loosen the main unit fixing screw of the product and pull out the main unit from the socket Fix the socket on the wall with screws Next insert the main unit into the socket and fasten the main unit with the main unit fixing screw 29 5 or more 22 0 2 2 M4 or 2 ø4 5 or more Mounting Dimensions Unit mm 59 0 3 Main unit fixing screw Socket Main unit Threaded hole for fixing the main un...

Page 3: ...ground the ground terminal through minimum resistance The length and thickness of the grounding cable should be as short and thick as possible Directly connect the lead from the ground terminal terminal no 8 of the product to the ground Do not carry out daisy chained inter ground terminal wiring The product is sensitive to static electricity exercise care in operating it Before you operate the pro...

Page 4: ...CAT III For measurements performed in the building installation Distribution board circuit breaker etc IV CAT IV For measurements performed at the source of the low voltage installation Overhead wire cable systems etc EMC standards CE EN 61326 1 Class A Table 2 EN 61326 2 3 The instrument continues to operate at a measurement accuracy of within 20 of the range during testing EN 55011 Class A Group...