5-39
IM XL100C-E
1
2
3
4
5
6
7
App
Index
Standard Protocol
p3
Monitor page access authentication enable/
disable
Enable:
USE
Disable:
NOT
p4
Operator page enable/disable
Enable:
USE
Disable:
NOT
p5
Operator page access authentication
enable/disable
Enable:
USE
Disable:
NOT
Query
YG?
Example
Enable the Web server function, the monitor
page, the monitor page access authentication,
the operator page, and the operator page access
authentication.
YG USE,USE,USE,USE,USE
Description • For details on the settings of the Ethernet, the
types of Web pages that can be displayed,
and access control, see “Web Server” in
section 1.2, “Explanation of Functions.”
• The settings changed with this command are
applied when they are saved using the XE
command.
YL
Sets the operation of the Modbus
master function
Syntax
YL p1,p2,p3<terminator>
p1
Read cycle
100MS, 200MS, 500MS
,
1S
,
2S
,
5S
, or
10S
p2
Communication timeout value
100MS, 200MS, 500MS
,
1S
,
2S
,
5S
,
10S
, or
1MIN
p3
Retrials
OFF
,
1
to
5
,
10
, or
20
Query
YL?
Example
Set the read cycle to 500 ms, timeout to 250 ms,
and retrials to 2.
YL 500MS,250MS,2
Description • This command is valid when the serial
interface protocol is set to “Master.” For serial
interface settings, see chapter 3, “Serial
Interface.”
• The settings changed with this command are
applied when they are saved using the XE
command.
YM
Sets the command of the
Modbus master function
When not setting a command
Syntax
YM p1,p2<terminator>
p1
Registration number
1
to
32
p2
Presence or absence of the command
OFF
Query
YM[ p1]?
Example
Do not set a command to command registration
number 1.
YM 1,OFF
When setting a command
Syntax
YM p1,p2,p3,p4,p5,p6,p7<terminator>
p1
Registration number
1
to
32
p2
Presence or absence of the command
ON
p3
First channel number
C01
to
C30
(corresponds to CO01 to
CO30),
CO01
to
CO32
p4
Last channel number
C01
to
C30
(corresponds to CO01 to
CO30),
CO01
to
CO32
p5
Slave device address (1 to 247)
p6
First register number
30001
to
39999,
300001
to
365535,
40001
to
49999,
400001
to
465535
p7
Type of data assigned to the register
INT16
,
UINT16
,
INT32_B
,
INT32_L
,
UINT32_B
,
UINT32_L
,
FLOAT_B
, or
FLOAT_L
Query
YM[ p1]?
Example
Register the following command in command
registration number 2: Read the 32-bit signed
integer data that is assigned to registers 30003
(upper 16 bits) and 30004 (lower 16 bits) of the
slave device at address 5 into C02 of the XL100.
YM 2,ON,C02,C02,5,30003,INT32_B
Description • This command is valid when the serial
interface protocol is set to “Master.” For serial
interface settings, see chapter 3, “Serial
Interface.”
• The settings changed with this command are
applied when they are saved using the XE
command.
YU
Sets the contents to be
transmitted by e-mail.
When sending the changes in the alarm status
Syntax
YU p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,
p11,p12<terminator>
p1
Content to be sent
ALARM
p2
Enable/Disable recipient 1
ON
or
OFF
p3
Enable/Disable recipient 2
ON
or
OFF
p4
Reserved
p5
Reserved
p6
Reserved
p7
Reserved
p8
Enable/disable attachment of instantaneous
data
ON
,
OFF
5.7 Basic Setting Commands