1-7
IM 04L57B01-01EN
Overview and Functions
1
2
3
4
5
6
App
1.2.9
Data Dropout Detection (GX/GP/GM)
The GX/GP/GM can detect GX70SM data acquisition dropouts caused by communication
errors or the like by collecting the GX70SM data serial numbers.* When the data serial
number received from the GX70SM does not change over a specified period, the GX/GP/
GM decides that a data dropout has occurred.
The occurrence of data dropouts can be output and recorded as alarms.
You can view the alarms that have occurred on the monitor view. Further, they can be used
to trigger internal switches, relay output, and e-mail transmission.
* Serial numbers assigned to data entries sampled by the GX70SM
Timeout
Read cycle
Data serial number
101
102
103
104
104
•
•
• • •
104
•
•
• • •
No change in data serial number
Alarm output
Data dropout detection
1.2.10 Device Information Output for Wireless Input Unit Errors (GX/GP)
When a battery error, operation error, communication disconnection, or the like occurs on
the GX70SM, device information can be output using a FAIL relay (/FL1 option).
1.2.11 Using the GX70SM as a Standalone Data Logger
The GX70SM can be used as a standalone data logger.
By mounting the GX70SM in a vehicle, it can be used to record the temperature, humidity,
and the like when transporting fresh foods, art objects, and so on in a truck.
When using the GX70SM as a standalone data logger, turn off the wireless function.