19
IM 04L21B01-02EN
Setting the Input Range
Configure the FX so that it measures temperature on measurement channel 1 and flow
rate on measurement channel 2.
Setting the Temperature Measurement Channel, the Input Range, and the Tag
Type T
thermocouple
Channel 1
0.0 to 200.0
°
C
FX
Setup Item
Description
Number in the Figure
Channel
Use channel 1.
1
Tag
TI-001
2
Sensor
Type T thermocouple
3
Input range
0.0 to 200.0°C
4
(1) Input Range
Press
MENU
(switch to the setting mode).
Select the
Menu
tab >
Meas channel
>
Range, Alarm
.
1
4
3
Setting Procedure
1.
Display the operation mode screen.
2.
Press
MENU
once to display the setting menu.
3.
Press the
down arrow key
twice to select
Meas channel
.
4.
Press the
right arrow key
once.
Select the Range, Alarm.
Setting the Functions and Operations