<Appendix 6. Multiple Analog Output (MAO) Block>
A6-4
IM 01S01C01-01EN
A6.4 Status Transitions
Note that inputs IN_1 – IN_8 status are not transferred to LCD Transducer Block as is when the following
settings are made.
Setting
Status transition (high-level system priority)
When MAO function block is in O/S mode
Bad – Out of Service – No Limit
When fault state to value x = 0 (freeze) (x: 1 to 8)
Bad – No comm, with LUV – Const
When fault state to value x = 1 (present) (x: 1 to 8)
Bad – No comm, no LUV – Const
When no output is connected to IN_1 – IN_8
Bad – Not Connected – No Limit
The MAO function block CHANNEL is 0
Bad – Configuration Error – <received limit (*)>
(*) received limit: Same as IN_1 – IN_8 status
Something other than the above
Same as IN_1 – IN_8 status
A6.5 Parameter list display
Relative
Index
Parameter
Write
Mode
Valid
Range
Initial
Value
View
Description/Remarks
1 2 3 4
0
BLOCK_HEADER Block
Tag
=O/S
Displays Block Tag, DD Revision, Execution Time
and other MAO function block information.
1
ST_REV
--------
--------
2
2
2
2 Describes the revision level of parameters for
setting the MAO function block. The revision
is updated when set values are changed. This
parameter is used to check for parameter changes.
2
TAG_DESC
Null
A universal parameter intended for storing
comments describing tag data.
3
STRATEGY
0
2 The strategy field is a universal parameter used by
a high-level system to identify function blocks.
4
ALERT_KEY
1-255
0
1 Key information used to identify the location
at which an alert occurred. Generally, this is a
universal parameter used by a high-level system
to identify specific areas in a plant that are under
the control of specific operators to distinguish
necessary alarms only.
5
MODE_BLK
4
4
A universal parameter that represents block
operating condition. It comprises the Actual, Target,
Permit and Normal modes.
6
BLOCK_ERR
--------
--------
2
2
Indicates error status of the MAO function block.
The following bits are used by the MAO function
block.
bit1: Block Configuration Error
bit 4: LO mode
bit 15: O/S mode
7
CHANNEL
O/S
1
2 A means for theoretically accessing LCD
Transducer Block. It cannot be used on the FVX110.
8
IN_1
0
5
5
This is an input (input 1) for the MAO function block.
9
IN_2
0
5
5
This is an input (input 2) for the MAO function block.
Summary of Contents for FVX110
Page 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Page 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Page 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Page 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Page 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Page 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...