<Appendix 6. Multiple Analog Output (MAO) Block>
A6-3
IM 01S01C01-01EN
A6.3 Fault State
Blocks and inputs in the MAO function block that are not in the normal state transition to the fault state status.
Use the FSTATE_STATUS parameter to confirm inputs in the fault state status.
A6.3.1 Transition to Fault State
If the input status stays in the Bad status for longer than the time set using FSTATE_TIME, the input transitions
to the fault state status. When the MAO function block is in LO mode, all inputs transferred to LCD Transducer
Block transition to the fault state status.
A6.3.2 Clearing a Fault State
Run the MAO function block in Auto mode to change the status of inputs to something other than Bad to clear
fault state status.
A6.3.3 Fault State Operation
Operation in fault state status is defined by MO_OPTS.
MO_OPTS
Definition
bit
Name
0
Fault state to value 1
Operation when input 1 is in the fault state
1
Fault state to value 2
Operation when input 2 is in the fault state
2
Fault state to value 3
Operation when input 3 is in the fault state
3
Fault state to value 4
Operation when input 4 is in the fault state
4
Fault state to value 5
Operation when input 5 is in the fault state
5
Fault state to value 6
Operation when input 6 is in the fault state
6
Fault state to value 7
Operation when input 7 is in the fault state
7
Fault state to value 8
Operation when input 8 is in the fault state
8
Use fault state value on restart 1
Operation when input 1 is in the fault state at restart
9
Use fault state value on restart 2
Operation when input 2 is in the fault state at restart
10
Use fault state value on restart 3
Operation when input 3 is in the fault state at restart
11
Use fault state value on restart 4
Operation when input 4 is in the fault state at restart
12
Use fault state value on restart 5
Operation when input 5 is in the fault state at restart
13
Use fault state value on restart 6
Operation when input 6 is in the fault state at restart
14
Use fault state value on restart 7
Operation when input 7 is in the fault state at restart
15
Use fault state value on restart 8
Operation when input 8 is in the fault state at restart
Use Fault state to value 1 – Fault state to value 8 to set fault state operation either to transfer the value prior to
fault state status to LCD Transducer Block (0: freeze) or to transfer FSTATE_VAL 1 – FSTATE_VAL 8 to LCD
Transducer Block (1: present).
When the Use fault state value on restart 1 – Use fault state value on restart 8 bit is on, values set by FSTATE_
VAL 1 – FSTATE_VAL 8 are used as default values at restart. (When this bit is not on, the value stored in IN_1
– IN_8 prior to restart is used as the default value after restart.)
The status of inputs in fault state status transitions from “Bad – No comm with LUV – Const” or “Bad – No
comm, no LUV – Const.” (Refer to Appendix 6.4)
Summary of Contents for FVX110
Page 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Page 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Page 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Page 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Page 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Page 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...