A2-38
IM 34M06C11-01E
(8) F3XD32-3F/F3XD32-4F/F3XD32-5F DC Input Modules
Item
Specifications
F3XD32-3F
F3XD32-4F
F3XD32-5F
Input type
DC voltage
Number of points
32
Common line type
8 points/common line
Isolation method
Photocoupler isolation
Withstanding voltage
1500V AC for one minute between the group of terminals for external connection and the
internal circuit
Rated input voltage
24V DC
12V DC
5V DC
Operating voltage range
20.4 to 26.4V DC
10.2 to 13.2V DC
4.5 to 5.5V DC
Rated input current
4.1mA/point (24V DC)
4.1mA/point (12V DC)
4.0mA/point (5V DC)
Input impedance
5.9k
Ω
2.9k
Ω
1.3k
Ω
Operating
voltage/current
ON
16.0V DC min.
3.2mA min.
8.0V DC min.
2.6mA min.
3.5V DC min.
2.0mA min.
OFF
5.8V DC max.
0.9mA max.
3.4V DC max.
1.0mA max.
1.0V DC max.
0.2mA max.
Response time
OFF
→
ON
Input sampling time can be specified for 5 steps : Always (0μs), 62.5μs, 250μs, 1ms and
16ms
*1
ON
→
OFF
Input sampling time can be specified for 5 steps : Always (0μs), 62.5μs, 250μs, 1ms and
16ms
*1
Interrupt
*2
Can be specified for each input point
Dissipating current
75mA (5V DC)
Input display
LED (lit when input is turned on)
External connection
One 40-pin connector
Weight
120g
Maximum ratio of inputs
turned on simultaneously
100%
*1:
These values are applicable when using the module with CPU module F3SP22, F3SP28, F3SP38, F3SP53,
F3SP58, F3SP59, F3SP66, F3SP67, F3SP71 or F3SP76 module. If other CPU modules are used, the values are
the same as those for F3XD32-
F modules. The actual response time is obtained by adding about 100
s for
OFF
ON and about 300
s for ON
OFF to the specified value.
If the input sampling time is set to a very small value, the modules become susceptible to noise. In such a case,
implement countermeasures against noise as described in Section A3.4 "Noise Control Considerations" and Section
A3.9 "CE Marking Compliance".
*2:
If input interrupt is to be used, set the input sampling time to 62.5
s or more.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...