A4-6
IM 34M06C11-01E
A4.3.3
Indicating Problem Severity and Status of Output
Module
The FA-M3 indicates the presence or absence of failures by the LEDs in the upper
section of the CPU module, classifying them into major, moderate and minor failures.
Tables A4.1 to A4.3 summarize the failure severity levels and the status of the output
module in each case.
See the Fiber-optic FA-bus Module and Fiber-optic FA-bus Type 2 Module, FA-bus Type
2 Module (IM 34M06H45-01E) for details on how the FAIL-signal contact output and
output module work if a failure arises in a transmission line, such as a fiber-optic cable,
in an application where a fiber-optic FA-bus type 2 module is in use.
Table A4.1 Failure Severity Levels and Status of Output Module
(when the CPU module is F3SP21/25/35 or F3FP36)
Severity
Level
LED
Indication
Effect Probable
Cause
Status of FAIL-signal
Contact Output
Status of Output Module
Between
FAIL1
and COM
Between
FAIL2
and COM
Output modules
other than
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N,
Y
□□□□□
*4
Major
Green
RDY
lamp is
off.
The core
hardware is
disabled.
•
CPU error
•
Memory crash
Shorted
Open
Default:
RESET
Can be set
globally on a
module basis.
Setting
ignored.
The status is
always
HOLD.
Moderate
Red ERR
lamp is
lit.
The user
program cannot
be started or
run any further.
•
Program error
P
*1
•
I/O comparison error
P
*1
•
I/O module error
P
*1
•
Memory error
•
SPU error
•
Instruction error
P
*1
•
Scan timeout
P
*1
•
Startup error
•
Invalid instruction found
•
Number of I/O points
exceeded
•
ROM pack error
•
Subroutine error
P
*1
•
Interrupt error
•
Subunit communication
error
P
*2
Shorted
Open
Default:
RESET
Can be set
globally on a
module basis.
Default:
RESET
Can be set
globally on a
module basis.
Minor
Yellow
ALM
lamp is
lit.
The program
can still run In
spite of a
failure.
•
Momentary power
failure
P
*5
•
Inter-CPU
communication error
•
Subunit transmitter
switching has occurred
P
*3
• FA link error
Open
Shorted
Operation
continues
Operation
continues
*1:
The severity level of this error item can be set using the Error-time Action field under Operation Control of the
Configuration. Setting the field to "Stop" indicates a moderate failure whilst setting it to "Run" indicates a minor
failure. The default value is "Stop" (moderate failure).
*2:
The severity level of this error item can be set using the Error-time Action field under Operation Control of the
Configuration. Setting the field to "Stop" indicates a moderate failure whilst setting it to "Run" indicates a minor
failure. The default value is "Run" (minor failure).
*3:
When using F3SP21, F3SP25 or F3SP35 CPU modules Rev. 8 or later or F3FP36.
*4:
Output relays (Y
□□□□□
) of the advanced modules.
*5:
When supply voltage abnormality is detected, output modules behave differently depending on whether the standard
mode or immediate detection mode is selected. Behaviors during momentary power failure in each mode are as
follows:
Supply Voltage
Abnormality
Detection mode
Status of FAIL-signal Contact Output
Status of Output Module
Between FAIL1 and
COM
Between FAIL2 and
COM
Output modules
other than
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N,
Y
□□□□□
*4
Standard mode
Open
Shorted
Hold
Hold
Immediate
detection mode
Shorted
Open
Reset
Hold
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...