A3-26
IM 34M06C11-01E
A3.6
Wiring I/O Modules
A3.6.1
Re-checking Specifications
CAUTION
- Re-check the I/O specifications for the input/output modules. Note that applying a
voltage or current that exceeds the maximum permissible input voltage or current of
an input module or a voltage or current that exceeds the maximum switching
capacity of an output module will lead to machine failure, physical damage or fire
hazard.
- To avoid electrical shock, turn off the power before wiring.
- Make sure that the polarity of power terminals is correct.
A3.6.2
Wiring Materials
(1) Wire
Method of External
Connection
Compatible Conductor Size
Temperature
Rating
Material
Terminal block
AWG22 to 14 (0.33 to 2.1mm
2
)
75°C min
Copper
Connector
Soldered
AWG23 or less (0.26mm
2
or less)
Crimp-on
AWG28 to 24 (0.08 to 0.20mm
2
)
Pressure-welded
AWG28 (0.08mm
2
); 1.27mm pitch
flat cable
To ensure that a system incorporating this module conforms to the CE Marking, use
shielded cables. By properly grounding the shield, noise emission and receipt will be
reduced. For more information on shielded cables, see Section A3.9.1 "Cable Routing
Considerations".
(2) Terminal Screws and Crimp-on Terminals
The I/O modules have an M3.5-screw terminal block each. The following crimp-on
terminals are recommended for connecting to I/O modules:
Under 7mm
FA030601.VSD
Figure A3.23 Crimp-on Terminals
Vendor
Model
Compatible Conductor
Crimping Torque
Japan Solderless
Terminal Mfg Co., Ltd.
V1.25-M3
AWG22 to 18
(0.33 to 0.82mm
2
)
(Copper wire)
0.8N
m
(7.1 lbf
in)
Nippon Tanshi Co., Ltd.
RAV1.25-3.5
Japan Solderless
Terminal Mfg Co., Ltd.
V1.25-M4
Japan Solderless
Terminal Mfg Co., Ltd.
V2-M4
AWG16 to 14
(1.3 to 2.1mm
2
)
(Copper wire)
Note
When crimping terminals, be sure only to use the tool specified by each terminal
manufacturer.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...