A2-77
IM 34M06C11-01E
(27) F3YD64-1A Transistor Output Module
Item
Specifications
Item
Specifications
Output type
Transistor contact
(sink type)
Service life
Mechanical
─
Electrical
─
Number of points
64
Surge protector
*1
Zener diode
Common line type
8 points/common
Fuse
None
Isolation method
Photocoupler isolation
Dissipating current
275mA (5V DC)
Withstanding voltage
1500V AC for one
minute between the
group of terminals for
external connection
and the internal circuit
Output display
*2
LED (Lit when output is on)
Status displayed for 32 points
selected by a switch
Rated load voltage
(Operating load
voltage range)
DC
24V DC
(20.4 to 26.4V DC)
Output status when the
program stops
HOLD/RESET
*3
When a sequence CPU
module is used:
Default: RESET
Can be set globally on a
module-by-module basis.
*4
AC
─
When a BASIC CPU module is
used:
No setting function
The status is always HOLD
Maximum load current
0.1A/point
0.4A/common line
Response
time
OFF
→
ON
1ms max.
ON
→
OFF
1ms max.
External power supply
24V DC, 150mA
ON voltage
0.5V DC max.
External connection
Two 40-pin connectors
Off-time leak current
0.1mA max.
Weight
160g
*1:
If an inductive load, such as a relay, is to be connected, a surge protector is also required on the load side. Connect
a surge protector or a diode across the load nearby so that the module output terminal voltage will not exceed the
specified operating load voltage range. For details, see Subsection A3.6.5, “Connecting Output Devices.”
*2:
The contact operation of the output block of the circuit and the LED display operate independently and thus may be
inconsistent in the event of an error.
*3:
For information on the module’s behavior during a CPU failure, see subsection A4.3.3, “Indicating Problem Severity
and Status of Output Module.”
*4:
When F3SP22, F3SP28, F3SP38, F3SP53, F3SP58, F3SP59, F3SP66, F3SP67, F3SP71 or F3SP76 module is
used, this setting can be specified in 16-point units.
Note
Differences between F3YD64-1F and F3YD64-1A
- For F3YD64-1F, the output status can be configured to HOLD or RESET in the
event of a major sequence CPU module failure when the F3SP22, F3SP28,
F3SP38, F3SP53, F3SP58, F3SP59, F3SP66, F3SP67, F3SP71 or F3SP76 CPU
module is used. For other CPU modules, the output is always HOLD in the event
of a major sequence CPU module failure.
- For F3YD64-1A, the output status is always HOLD in the event of a major sequence
CPU module failure regardless of the CPU module used.
For more information, see Section A4.3.3 "Indicating Problem Severity and Status of
Output Module."
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...