10. GENERAL SPECIFICATIONS
10. GENERAL SPECIFICATIONS
10.1 Standard Specifications
Refer to IM 01C25R03-01E for FOUNDATION
Fieldbus protocol type marked with “
”
Performance Specifications
See General Specifications sheet, GS 01C25R01-01E.
Functional Specifications
STANDARD SPECIFICATIONS
SPAN AND RANGE LIMITS
Differential Pressure (DP)
T1001E.EPS
50 to 10000
–10000 to 10000
0.025 to 5 kgf/cm
2
–5 to 5 kgf/cm
2
5 to 1000
–1000 to 1000
25 to 5000
–5000 to 5000
2 to 400
–400 to 400
10 to 2000
–2000 to 2000
0.5 to 100
–100 to 100
2.5 to 500
–500 to 500
Span
Range
Span
Range
mmH
2
O(/D4)
mbar(/D3)
inH
2
O(/D1)
kPa
H
M
10 to 1000
–1000 to 1000
1 to 100
–100 to 100
0.4 to 40
–40 to 40
0.1 to 10
–10 to 10
Span
Range
L
Measurement
Span/Range
Static Pressure (SP)
Absolute Pressure
T1002E.EPS
10 to 250
0 to 250
10 to 250
0 to 250
145 to 3600
0 to 3600
1 to 25
0 to 25
Span
Range
kgf/cm
2
abs(D4)
bar abs(D3)
psia(/D1)
MPa abs
M
H
10 to 160
0 to 160
10 to 160
0 to 160
145 to 2300
0 to 2300
1 to 16
0 to 16
Span
Range
L
Measurement
Span/Range
Gauge Pressure (Sealed gauge)
T1003E.EPS
10 to 250
–1 to 250
10 to 250
–1 to 250
145 to 3600
–14.5 to 3600
1 to 25
– 0.1 to 25
Span
Range
kgf/cm
2
(D4)
bar(/D3)
psi(/D1)
MPa
M
H
10 to 160
–10 to 160
10 to 160
–10 to 160
145 to 2300
–14.5 to 2300
1 to 16
–1 to 16
Span
Range
L
Measurement
Span/Range
External Temperature (ET) (PT100 ohm)
T1004E.EPS
10 to 1050
73 to 1123
0 to 2200
18 to 1890
–328 to 1562
–459 to 3500
10 to 1050
–200 to 850
–273 to 1927
L
M
H
Span
Range
Fixed Temperature
K
°
F
°
C
Measurement External
Temperature Span/Range
FUNCTIONAL SPECIFICATIONS
Output “
”
Dual output (Both analog and pulse/contact output can
be obtained simultaneously).
In this case refer to the item “Wiring example for
analog output and status/pulse output”.
Analog Output “
”
Two wire 4 to 20 mA DC output, user-selectable for
Differential Pressure, Static Pressure, External Tem-
perature or Flow Rate signal.
Failure Alarm “
”
Analog output status at CPU failure and hardware error
Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: –2.5%, 3.6 mA DC or less
Pulse/Contact Output (for HART protocol type)
Pulse or status output is selected by parameter setting.
Transistor contact output (sink type).
Contact rating: 10.5 to 30 V DC, 120 mA DC max.
Low level: 0 to 2 V DC. (Refer to Figure 1)
HIGH level
LOW level
0 to 2 V
0V
F1001E.EPS
Figure 10-1. High and low level (Pulse output)
Pulse Output (for HART protocol type)
Scaled pulse or frequency pulse output is selected by
parameter setting.
Scaled Pulse Output Function
(for HART protocol type)
Pulse is output by the unit of the scaled flow rate.
Scaled pulse can be totalized.
Frequency Output Function
(for HART protocol type)
Number of pulses output per second at 100% of output.
Pulse frequency: Max. 10 kHz
Duty cycles: Approx. 50% (1:2 to 2:1)
Contact Output Function
(for HART protocol type)
High or low alarm
Status signal output mode can be reversed (ON/OFF).
Table 10.1. Signal Output
T1005E.EPS
Differential
pressure
Static
pressure
External
temperature
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Flow rate
*1
Total flow
*1
4-20mA
Pulse output
High/Low
alarm
Output
*1:
When Measurement Function Code B is specified.