IM 01C25R03-01E
5-5
5. CONFIGURATION
T0504-2.EPS
13
FasDllSubscriber
SynchronizationDlcep
Not used for EJX.
14
FmsVfdId
Sets VFD for EJX to be
used.
0x1: System/network
management VFD
0x1234: Function block
VFD
15
FmsMaxOutstanding
ServiceCalling
Set 0 to Server. It is not
used for other applications.
16
FmsMaxOutstanding
ServiceCalled
Set 1 to Server. It is not
used for other applications.
17
FmsFeatures
Supported
Indicates the type of
services in the application
layer. In the EJX, it is
automatically set according
to specific applications.
Sub-
index
Parameter
Description
12
FasDllSubsriberTime
WindowSize
Not used for EJX.
33 VCRs are factory-set as shown in the table below.
Table 5.5
VCR List
Index
(SM)
VCR
Number
Factory Setting
293
For system management (Fixed)
1
294
Server (LocalAddr = 0xF3)
2
295
Server (LocalAddr = 0xF4)
3
296
Server (LocalAddr = 0xF7)
4
297
Trend Source (LocalAddr = 0x07,
Remote Address=0x111)
5
298
Publisher for AI1 (LocalAddr = 0x20)
6
299
Alert Source (LocalAddr = 0x07,
Remote Address=0x110)
7
300
Server (LocalAddr = 0xF9)
8
301
Publisher for AI2 (LocalAddr = 0x21)
9
302 to 315
Not used.
10 to 33
T0505.EPS
5.5.2 Function Block Execution Control
According to the instructions given in Section 5.3, set
the execution cycle of the function blocks and schedule
of execution.
5.6 Block Setting
Set the parameter for function block VFD.
5.6.1 Link Object
A link object combines the data voluntarily sent by the
function block with the VCR. The EJX910A has 40
link objects. A single link object specifies one combi-
nation. Each link object has the parameters listed in
Table 5.6. Parameters must be changed together for
each VCR because the modifications made to each
parameter may cause inconsistent operation.
Table 5.6
Link Object Parameters
T0506.EPS
Sub-
index
Parameters
Description
1
LocalIndex
Sets the index of function
block parameters to be
combined; set “0” for Trend
and Alert.
2
VcrNumber
Sets the index of VCR to
be combined. If set to “0”,
this link object is not used.
3
RemoteIndex
Not used in EJX. Set to “0”.
5
StaleCountLimit
Set the maximum number
of consecutive stale input
values which may be
received before the input
status is set to BAD. To
avoid the unnecessary
mode transition caused
when the data is not
correctly received by
subscriber, set this
parameter to “2” or more.
4
ServiceOperation
Set one of the following.
Set only one each for link
object for Alert or Trend.
0: Undefined
2: Publisher
3: Subscriber
6: Alert
7: Trend
Set link objects as shown in Table 5.7.
Table 5.7
Factory-Settings of Link Objects (example)
T0507.EPS
Index
Link Object #
Factory Settings
30000
AI1.OUT
→
VCR#6
1
30001
Trend
→
VCR#5
2
30002
Alert
→
VCR#7
3
30003
AI2.OUT
→
VCR#9
4
30004 to
30039
Not used
5 to 40