<11. General Specifications>
11-1
IM 01C27F01-01EN
11. General Specifications
11.1 Standard Specifications
Communication protocol
ISA100.11a protocol
Data rate
250 kbps
Frequency
2400 - 2483.5 MHz license free ISM band
Radio security
AES 128 bit codified
RF Transmitter power
Max. 11.6 dBm (fixed)
Antenna
+2 dBi Omni directional monopole type
Span and range limits
(For EJX510B, values are in absolute and lower
range limits are 0.)
Measurement
Span/Range
MPa
psi
(/D1)
bar
(/D3)
kgf/cm
2
(/D4)
A
Span
8 to 200
kPa
1.16 to 29
0.08 to 2 0.08 to 2
Range
–100 to
200 kPa
–14.5 to 29
–1 to 2
–1 to 2
B
Span
0.04 to 2
5.8 to 290
0.4 to 20 0.4 to 20
Range
–0.1 to 2 –14.5 to 290
–1 to 20
–1 to 20
C
Span
0.2 to 10
29 to 1450
2 to 100
2 to 100
Range
–0.1 to 10 –14.5 to 1450 –1 to 100 –1 to 100
D
Span
1 to 50
145 to 7200 10 to 500 10 to 500
Range
–0.1 to 50 –14.5 to 7200 –1 to 500 –1 to 500
Performance specifications
Refer to GS 01C27F01-01EN.
Update Time
Measurement
mode
Differential
pressure
Pressure
Continuous
100 ms
100 ms
Intermittent
0.5 to 3600 s
selectable
0.5 to 3600 s
selectable
The transmitter shifts to the countinuous mode
when the update time is set to 0.5 second.
Power Supply Specifications
Battery:
Use the dedicated battery pack.
Rated voltage: 7.2 V
Rated capacity: 19 Ah
External Power Source:
Rated voltage: 10.5 to 30 V DC
Rated current: 36 mA
Output
Wireless (ISA100.11a protocol) 2.4GHz signal
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within
the lower and upper range limits of the capsule.
External Zero Adjustment
External zero is continuously adjustable with
0.01% incremental resolution of span. Re-range
can be done locally using the digital indicator
with range-setting switch.
Integral Indicator (LCD display)
5-digit numerical display, 6-digit unit display
and bar graph. The indicator is configurable
to display one or up to two of the following
variables periodically.;
Pressure and temperature.
Burst Pressure
A, B and C capsule: 30MPa
D capsule: 132MPa
Self Diagnostics
Capsule failure, amplifier failure,
configuration error, battery alarm,
wireless communication alarm,
and over-range error for process variables.
Ambient Temperature Limits
−40 to 85ºC(−40 to 185°F)
−30 to 80ºC(−22 to 176°F) LCD visible range
Process Temperature Limits
−40 to 120ºC(−40 to 248°F)
Ambient Humidity Limits
0 to 100% RH