<3. Installation>
32
IM 01C25A01-01E
IMPORTANT
The transmitter should be installed at least 600 mm below
the high pressure (HP) process connection to ensure a
positive head pressure of fill fluid. Pay special attention to
vacuum applications.
If it can not be installed at least 600 mm below the HP
process connection, please use the equation below:
h=
× 0.102
[mm]
(P–P0)
ds
h: Vertical height between the HP process connection
and the transmitter (mm)
h≤0: Install the transmitter at least h (mm) below the
HP process connection
h>0: Install the transmitter at most h (mm) above the
HP process connection
P: Pressure in the tank (Pa abs)
P0: Minimum working pressure limit of the transmitter (Pa
abs) See below table.
[For fill fluid code A, B, C, D, E]
Wetted parts
material
code
Capillary
length
Process connection size
code
2, 8
3
4,W
SW
1 to 5m
6790
3190
6 to 10m
10030
3520
SE
1 to 5m
6790
3190
6 to 10m
10030
3520
SY
1 to 5m
3190
6 to 10m
3520
HW
1 to 5m
19150
6140
6 to 10m
8290
TW
1 to 5m
9620
3620
6 to 10m
4210
UW
1 to 5m
9540
4750
6 to 10m
6050
[For fill fluid code 1, 2, 4]
Wetted parts
material
code
Capillary
length
Process connection size
code
2, 8
3
4,W
SW
1 to 5m
2570
320
6 to 10m
4680
530
SE
1 to 5m
2570
320
6 to 10m
4680
530
SY
1 to 5m
320
6 to 10m
530
HW
1 to 5m
10220
2050
6 to 10m
3450
TW
1 to 5m
4270
570
6 to 10m
960
ds: Specific gravity of fill fluid (at 25°C). See below table.
Fill fluid
code
A, 1, 4
B
C, 2
D
E
ds: Specific
gravity
1.07
0.94
1.09
1.90 to
1.92
1.09
F0308.ai
P
Low pressure side
High
pressure
side
(+)
(–)
0
h
Figure 3.8
Example of Installation to Tank
(Caution on Installation)
3.4 Mounting the Flushing
Connection Ring
3.4.1 Mounting to Pressure Detector
Section
The flushing connection ring is mounted to the pressure
detector section as shown in Figure 3.9.
At the factory shipment, the flushing connection ring is
already assembled and attached to process detector
section.
Ring holder
Spiral gasket
F0309.ai
View from pressure
detector section
Groove for
installing
spiral gasket
Pressure-detector section
Vent/Drain plug
Ring
Figure 3.9
Mounting to Pressure Detector Section
(1) Mount the ring holder on the ring and loosely tighten
the mounting screws.
(2) Place the spiral gasket in the ring groove. With the
ring correctly aligned and flush with the face of the
pressure detector, securely tighten each ring holder’s
mounting screws.
(3) Position the ring so that the vent/drain plugs are
aligned straight up and down.