<8. Setting Parameters>
8-16
IM 01C27C01-01EN
CAUTION
After setting the deep sleep mode by infrared
device configuration tool, keep the infrared port
of device away from any other infrared signals.
NOTE
• Transmitter becomes the stop state after
setting deep sleep mode and cannot reply
any request from the device configuration
tool via wireless communication.
• For this reason, there is the case that an
error is display on the device communication
tool via wireless communication.
• To wake up from deep sleep mode, please
pull battery pack and wait more than 30
seconds before attaching battery pack.
8.3.14 Switching to Silence Mode
This is a function to pause the instrument when
it cannot join the field wireless network after a
specified time has elapsed. This function is effective
in conserving battery power when, for example, the
installation of the field wireless integrated gateway
is delayed compared to that of field wireless
devices. The default value is 28800 seconds (8
hours). Thereafter, a cycle of a one-hour pause and
six-minute search is repeated until the instrument
can join the field wireless network.
• Procedure to call up the switch-to-silence
parameter (Radio Silence)
UAPMO block : Radio Silence
Set 0 to 2
31
seconds for the Radio Silence
parameter of the UAPMO block. If 0 is set, the
Radio Silence parameter is invalid. To start
from silence mode, either remove and insert
the battery pack, or use the provisioning device
tool or the device configuration tool via infrared
communication.