YOKOGAWA CL320 User Manual Download Page 1

 
 

 
 
 
 
 

Contents 

„

 Precautions for Safety Use of the Instrument 

1. Instrument Layout 
2. Measurement 

2.1 Preparation 

for 

Measurement 

2.2  AC Current Measurement 
2.3  How to Use Frequency Selector Button 
2.4  Peak Current Measurement 

3. Other Functions 

3.1 Auto-Power-Off 

Function 

3.2  Data Hold Function 
3.3 Optional 

Accessories 

4. Battery Replacement 
5. Specifications 
6.  Calibration and After-sales Service 

 
 
 
 
 

 

„

 Precautions for Safe Use of the Instrument 

When handling the instrument, ALWAYS observe all of the cautionary 

notes on safety given below. Yokogawa M&C Corporation is not at all 

liable for damage resulting from misuse of this product by the user 

that is contrary to these cautionary notes. 

Various symbols are used on the instrument and in this manual to 

ensure the product is used safety and to protect operators and prop-

erty from possible hazards or damage. The following safety symbols 

are used where appropriate. Read the explanations carefully and 

familiarize yourself with the symbols before reading the text. 

 

The instrument and this manual use the following safety symbols: 

 

Danger! Handle with Care. 

This symbol indicates that the operator must refer to an ex-

planation in the User’s Manual in order to avoid the risk of 

personal injury or death and/or damage to the instrument. 

 

Double Insulation 

This symbol indicates double insulation. 

 

AC Voltage/Current 

This symbol indicates AC voltage or current. 

 

Ground 

This symbol indicates ground (earth) 

 

WARNING 

Indicates that there is a possibility of serious personal injury or loss of 

life if the operating procedure is not followed correctly and describes 

the precautions for avoiding such injury or loss of life. 

CAUTION 

Indicates that there is a possibility of serious personal injury of dam-

age to the instrument if the operating procedure is not followed cor-

rectly and describes the precautions for avoiding such injury or dam-

age. 

NOTE 

Draws attention to information essential for understanding the opera-

tion and features. 

 

WARNING 

  Never make measurement on a circuit above 300V AC. 

  Do not use the instrument in an atmosphere where any flammable 

or explosive gas is present. 

  Do not attempt to make measurement in the presence of flamma-

ble gasses, fumes, vapor or dust. Otherwise, the use of the instru-

ment may cause sparking, which can lead to an explosion. 

  Avoid using the instrument if it has been exposed to rain or mois-

ture or if your hands are wet. 

  Do not exceed the maximum allowabIe input of any measurement 

range. 

  Never open the battery compartment cover when making meas-

urement. 

  Do not use the instrument if there is any damage to the casing or 

when the casing is removed. 

  Do not install substitute parts or make any modification to the in-

strument. Return the instrument to Yokogawa M&C or your dis-

tributor for repair or re-calibration. 

  Always switch off the instrument before opening the battery com-

partment cover for battery replacement. 

 

WARNING 

To avoid damage to the instrument or electric shock! 

The restrictions on the maximum voltage level for which the CL320 

testers can be used, depend on the over-voltage categories specified 

by the safety standards. These category specifications are formulated 

to protect operators against transient impulse voltage in power lines. 

 

Maximum Allowable Input

 

Function

 

OVERVOLTAGE CATEGORY III

 

200Arms AC 

Measuring circuit voltage : 300Vrms AC 

 

Over-voltage category I (CAT.I): 

  Signal level, special equipment or parts of equipment, telecommunication, 

electronic etc., with smaller transient over-voltages than CAT.II. 

Over-voltage category II (CAT.II) 

  Local level, appliance, portable equipment etc., with smaller transient 

over-voltages than CAT.III. 

Over-voltage category III (CAT.III): 

  Distribution level, fixed installation, with smaller transient over-voltages than 

CAT.IV. 

 

CAUTION 

  Be sure to set the Range switch to the "OFF" position after use. 

When the instrument will not be in use for a long period of time, 

Place it in storage after removing the battery. 

  Use a damp cloth and detergent for cleaning the instrument. Do not 

use abrasives or solvents. 

 

NOTE 

  Radiation immunity affects the accuracy of CL320 testers under the 

conditions specified in EN 61000-4-3:1997. 

  If equipment generating strong electromagnetic interference is 

located nearly, the testers may malfunction. 

 

1. Instrument Layout 

Range Switch

Open/Close Lever

Transformer

Data Hold Switch

Display

Data hold mode

indicator

Low battery indicator

Frequency

response of WIDE

Frequency

response of

50/60Hz

Unit of measurement

quantity

LCD

Hand Strap

Frequency Selector Switch

 

 

2. Measurement 

2.1 Preparation 

for 

Measurement 

WARNING 

Do not make measurement on a circuit above 300V AC. This may 

cause shock hazard or damage to the instrument or equipment under 

test. 
 

CAUTION 

  The jaw section is a delicate, precision sensor. Do not subject the 

jaw to unreasonably strong shock, vibration, or force when using it. 

  If dust gets into the tops of the jaws, remove it immediately. Do not 

close the jaws when dust is trapped in its joints as the sensor may 

break. 

 Please check that the Range switch is set to the desired position 

before measurement.

   

NOTE 

 During current measurement, keep the transformer jaws fully 

closed. Otherwise, accurate measurement cannot be made. The 

maximum measurable conductor size is approx. 24mm in diameter. 

  When measuring large current, the transformer jaws may buzz. 

This has no effect on the instrument’s performance or safety. 

 

2.2  AC Current Measurement 

 

(1)  Set the Range switch to the desired position. Current to measure 

should be within the selected measuring range. 

(2) Normal measurement :  

Press the jaw open/close lever to open the transformer jaws and 
close them over one conductor only. Measured current value is 
shown on the display. Earth leakage current or small current that 
flows through a grounded wire can also be measured by this 
method. 

Lo

ad

Lo

ad

Correct

Wrong

 

 
(3)  Measuring out of balance leakage current :   

Clamp onto all conductors except a grounded wire. Measured 
current value is shown on the display. 

Lo

ad

Note : In case of 3-phase 3-wire,
          clamp four wires for measurement.

3-phase 3-wire

1-phase 2-wire

Lo

ad

Note : In case of 1-phase 3-wire,
          clamp three wires for measurement.

 

 

2.3  How to Use Frequency Selector Button 

When high frequencies from such equipment as inverters are present 
in the circuit under test, the instrument measures AC current of not 
only 50Hz or 60Hz of fundamental frequency but also of these high 
frequencies and harmonics. 
To eliminate the effect of such high frequency noise and measure AC 
current of 50Hz or 60Hz fundamental frequency, a "high-cut" filter 
circuit in incorporated into the instrument which works when 
"50/60Hz" frequency response is selected with the Frequency Selec-
tor button. Cut-off frequency of "high-cut" filter is about 100Hz with 
attenuation characteristic of approx. -24dB/octave. 

NOTE 

Characteristic of -24dB/octiave means that signal magnitude declines 
to about one sixteenth of that at the initial frequency when frequency 
doubles. 
The Frequency Selector button has the following two positions. 

  WIDE (40Hz or more) : 

Permits measurement of currents of fundamental frequencies as 

well as currents of high frequencies generated by such equipment 

as inverters. 

  50/60Hz (40 to approx. 100Hz) : 

Filters out high frequency currents and measures current of fun-

damental frequency only. 

When the 

  button is pressed, "50/60Hz" mark is shown on the 

left side of the display. When the 

  button is pressed again, 

frequency response is switched to WIDE with "WIDE" mark shown on 
the display. 

(dB)

 f  (Hz)

Frequency

Per
cen

tage

Att

enu

ation

Frequency characteristics

All ranges WIDE

position

All ranges at 50/60Hz Position
(-24dB/oct)

 

Recently there has been increased use of power through inverters, 
switching regulators, etc. When the high frequency noise from such 
appliances leaks or flows into the ground through capacitors not 
filtering completely, the earth leakage breaker may trip even though 
there is no "actual" leakage. In such a case, the instrument do not 
give leakage current reading if "50/60Hz" frequency response is se-
lected. 
Take care readings with the 50/60Hz and WIDE frequency responses 
respectively to make effective use of the Frequency Selector button. 

 

3. Other Functions 

3.1 Auto-Power-Off 

Function 

This is a function to prevent the instrument from being left powered on 
and conserve battery power. The instrument automatically turns off 
about 10 minutes after the last switch or button operation. To return to 
the normal mode, turn the Range switch to OFF, then to the desired 
position. 

 

3.2  Data Hold Function 

This is a function to freeze the reading on the display. When the 

  button is pressed once, the current reading is held even though 

current under test varies. "

" mark is shown on the upper right 

corner of the display. 
To exit the data hold mode, press the 

 button again. 

NOTE 

When the auto-power-off function works while the instrument is in the 

data hold mode, data hold is cancelled. 

 

3.3 Optional 

Accessories 

Clamp Adapter Model 99025 (For AC current measurement only) 
Clamp Adapter Model 99025 is designed to increase the measuring 
capability of a clamp meter. With the use of the Clamp Adapter, you 
can not only extend current range over 2000A, but also clamp on a 
large bus-bar or conductor.   
(1)  Set the Range switch to the desired position. 
(2)  As shown in the figure right, clamp Model CL320 onto the pickup 

coil of Model 99025. 

(3)  Clamp Model 99025 onto the bus-bar or conductor under test. 
(4)  Take the reading on Model CL320 and multiply it by 10. 

 

NOTE 

The clamp adapter is not applicable to leakage current measurement. 
For detailed specification, refer to the Clamp Adapter User’s Manual. 
 

4. Battery Replacement 

WARNING

To avoid electric shock hazard, never try to replace batteries during 

measurement. 
 

CAUTION 

  Do not mix new and old batteries. 

  Make sure to install battery in correct polarity as indicated in bat-

tery compartment.

 

 

If the battery voltage becomes too low for the instrument to operate 
normally, "

" is shown on the display. Then, replace the battery. 

Note that when the battery is completely exhausted, the display 
blanks without "

" shown. 

(1)  Set the Range switch to the "OFF" position. 
(2)  Press in the hole on the battery compartment cover with the tip of 

a pointed object, then slide open the cover. 

(3)  Replace the battery observing correct polarity. Use two new 

LR-44 or SR-44 batteries. 

(4)  Slide the battery compartment cover back in place. 

 

 

5. Specifications 

„

 Instrument Specifications 

Measuring Ranges and Accuracy (at 23 ±5°C, relative humidity up to 75%) 
  AC Current 

 

Accuracy 

Frequency Selector Switch 

Ranges

Measuring 

range 

WIDE position 

50/60 position 

40mA 0 

to 

19.99mA 

200mA 0 to 199.9mA 

0 to 100.0A 

±2.0% rdg ±4dgt 
 (50/60Hz) 
±5.0% rdg ±6dgt 
 (40 to 400Hz) 

±3.0% rdg ±5dgt 
 (50/60Hz) 

200A 

100.1 to 199.9A

±5.0% rdg ±4dgt 
 (50/60Hz) 

±5.0% rdg ±5dgt 
 (50/60Hz) 

 

„

General Specifications 

  Operating System : Dual integration 

  Measurement Function : AC current 

  Display : Liquid crystal display with maximum counts of 1999 

  Overrange Indication : "1" flashes on the highest digit 

  Response Time : Approx. 2 seconds. 

  Sample Rate : Approx. 2 times per seconds. 

  Temperature and Humidity for Guaranteed Accuracy : 23°C ±5°C, 

relative humidity up to 75% without condensation 

  Operating Temperature and Humidity : 0 to 40°C, relative humidity 

up to 85% without condensation 

  Storage Temperature and Humidity : -10 to 50°C, relative humidity 

up to 75% without condensation 

  Effect of conductor position :   

  The difference between maximum and minimum values to a 10 

mm-dia conductor, at every part inside the jaws; 

      Within 5dgt for 0 to 50A 

      Within 2% for 50 to 200A 

  Effect of external magnetic field : 10 mA or less in proximity to a 

14.5 mm-dia conductor carrying 100 A 

  Effect of residual current : 10 mA or less in proximity to a 10 

mm-dia conductor carrying 50 A 

  Power Source : Two LR-44 or SR-44 battery 

  Battery Life : Approx. 15 hours (continuous) 

  Current Consumption : Approx. 5mA 

  Auto-power-off function : Turns power off approx. 10 minutes after 

the last switch operation 

  Withstanding Voltage : 3700V AC, 1 minute between electrical 

circuit and housing case or metal part of the jaws 

  Insulation Resistance : 10M

 or greater at 1000V between elec-

trical circuit and housing case or metal part of the jaws 

  Conductor Size : Approx. 24mm diameter max. 

  Dimensions : Approx. 60(W) x 149(H) x 26(D) mm 

  Weight : Approx. 120g 

  Safety Standard: EN 61010-1 

EN 61010-2-032 
(300V AC CAT III, Pollution degree2, indoor use) 

  EMC Standard :   EN 61326 

 EN 

55022 

  Accessories : LR44 batteries··························· 2 

Carrying case Model 93033······· 1 
User’s Manual ··························· 1 

  Optional Accessories : Clamp adapter Model 99025 

 

6.  Calibration and After-sales Service 

Should any failure occur while you are using the tester, follow the 
instructions given below. If the tester still fails to operate correctly and 
needs repair, contact the vendor from whom you purchased the in-
strument or the nearest Yokogawa M&C sales office. 

 

  Turn off the POWER switch once, then turn it back on again. 

  If the tester does not turn on, replace the battery with a new one. 

 
Calibration  
It is recommended that the instrument be calibrated once every year. 
 
 
 

 

YOKOGAWA M&C CORPORATION 
International Sales Dept. 

2-9-32 Nakacho, Musashino-shi, Tokyo, 180-8750 Japan 
Phone: 81-422-52-5716  Facsimile: 81-422-55-8654 

YOKOGAWA CORPORATION OF AMERICA (U.S.A.) 

Phone: 1-770-253-7000  Facsimile: 1-770-251-2088 

YOKOGAWA EUROPE B. V. (THE NETHERLANDS) 

Phone: 31-334-64-1611  Facsimile: 31-334-64-1610 

YOKOGAWA AMERICA DO SUL S. A. (BRAZIL) 

Phone: 55-11-5681-2400    Facsimile: 55-11-5681-1274 

YOKOGAWA ENGINEERING INSTRUMENTS KOREA CORPORATION (KOREA) 

Phone: 82-2-551-0660 to -0664    Facsimile: 82-2-551-0665 

YOKOGAWA AUSTRALIA PTY. LTD. (AUSTRALIA) 

Phone: 61-2-9805-0699  Facsimile: 61-2-9888-1844 

YOKOGAWA BLUE STAR LTD. (INDIA) 

Phone: 91-80-227-1513  Facsimile: 91-80-227-4270 

LTD. YOKOGAWA ELECTRIC (RUSSIAN FEDERATION) 

Phone: 7-095-737-7868  Facsimile: 7-095-737-7869 

 

KIM3E-2003.2 

User’s 

Manual

 

CL320 
Leakage Clamp-on Tester 

IM CL320

 

1st Edition: Apr. 2003 (MC) 

IM CL320 

Reviews: