![YOKOGAWA Centum VP Technical Information Download Page 169](http://html1.mh-extra.com/html/yokogawa/centum-vp/centum-vp_technical-information_3456521169.webp)
Appendix 2. ATEX Ex “ec”/ATEX Type “n” / UKEX Ex “ec” / UKEX Type “n”
App.2-20
TI 33Q01J30-01E
Appendix 2.5 ATEX Ex “ec”/ UKEX Ex “ec”
Information of A2BN5D
Applicable Standards
EN IEC 60079-0:2018
EN IEC 60079-7:2015 + A1:2018
EN 60079-11:2012
Markings
FIDI 21 ATEX 0071X
CML 22UKEX2105X
II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Applicable Models
A2BN5D
List of Parameters
Table List of Parameters (ATEX) of Base Plate for Barrier (A2BN5D)
Modules
Uo (V)
Io (mA)
Po (mW)
Ui (V)
Co (nF)
Lo (mH)
Remarks
A2BN5D
30
—
—
30
—
—
(*1)
*1:
The used P+F’s I.S. barriers determine the ultimate output parameters of the channel. Please refer to P+F’s instruction manual
for the parameter of P+F’s I.S. barriers.
Nov. 10, 2022-00