3. Cabling
3-11
TI 33Q01J10-01E
3.3
Connecting Ground Cable
Connect ground cables as follows:
CAUTION
• Connect the terminal connection type device to the ground terminal.
• Connect LPCKIT, YPCKIT, AFS40S/AFS40D, AFG40S/AFG40D, AFS20S/AFS20D,
AFG20S/AFG20D, ACB41, and ACB21 to the relay terminal of the ground bar for
connecting a ground cable with M5 screws.
• Connect a power cable of the plug-in device to a grounded socket. The cabinet is grounded
when the power cable is plugged in.
Nov. 1, 2001-00