< 5. Wiring >
5-14
IM 11M12D01-01E
5.3.3 Wiring and Piping for Blow back
Averaging Converter (AV550G)
Analog Output
(Averaged and Individual Output)
Contact Output
Contact Input
Power Supply
Blow back Solenoid Valve
High Temperature
Detector
Stop Valve
Calibration
Gas Line
Reference
Gas Line
Calibration
Gas Line
Reference
Gas Line
To ZA8F Flow Setting Unit
To ZA8F Flow Setting Unit
Instrument Air
Air Set
: If optional 24 V outputs are specified for solenoid valves (Option Code "/24"), no external
power supply for solenoid valves is required. The solenoid valves are powered from the AV550G
Averaging Converter. Never connect external power sources in the wiring for solenoid valves.
F5-17.ai
SV-CH1
SV-CH8
*
*
*
Figure 5.17 Typical Diagram for Blow back
5.3.4 Wiring and Piping for Automatic Calibration and Blow back
Averaging Converter (AV550G)
Analog Output
(Averaged and
Individual Output)
Contact Output
Contact Input
Power Supply
Span Gas Cylinder
(Instrument Air)
Zero Gas Cylinder
Pressure Reducing Valve
Solenoid
Valve
Flowmeter
Needle Valve
Calibration Gas Line
Instrument Air
Air Set
Needle Valve
Flowmeter
Reference
Gas Line
Solenoid
Valve
Blow back Solenoid Valve
High Temperature
Detector
Note : If optional 24 V outputs are specified for solenoid valves (Option Code "/24"), this system cannot be established.
This is because the contact to activate a solenoid valve is used in common for automatic calibration and blow back.
F5-18E.ai
SV-CH1
SV-CH8
SV-COM
DO1~4
Figure 5.18 Typical Diagram for Automatic Calibration and Blow back