<5. Basic Operating Procedures>
53
IM 01E24A01-01EN
5.4.2 Setting example of Numeric type
Data: Flow rate span
The following is the procedure of changing the Flow rate
span as Numeric type parameter.
Display Menu Path:
Device setup ► Detailed setup ► Pro var ► Volume ► Span
NOTE
Be sure to set the Flow rate unit in the beginning when
the Flow rate unit and Flow span value are changed at
the same time.
When the unit is changed, the value of flow rate span is
converted to related values automatically according to
the unit change.
F0524.ai
Volume
Time unit
/h
Span +7200.00
Setting download
00 : 00
SET
SFT
INC
▲
▼
Specify the Flow rate span unit.
Move cursor with [INC] and [DEC] according
to the menu path above, and select the
“Span” then push [SET].
F0525.ai
Span
+7200.00
+2200.00
+0.00001 +999999
00 : 00
SET
SFT
INC
The switch's functionality of setting the Flow
rate span is as below:
Plus/minus and mumeric change: [INC]
Movement on digits: [SFT]
Determination of parameter: [SET]
L
: Minimum value
U
: Maximum value
Push [SET] to decide while the value of Flow
rate span is blinking. The screen returns to
the setting page after the setting.
5.4.3 Setting Example of Alphanumeric type
Data: Tag No.
The following is the procedure of changing the Tag
No. as Alphanumeric type parameter according to the
specification of HART protocol.
Display Menu Path:
Device setup ► Detailed setup ► Device info ► Order info ► Tag No.
F0526.ai
Device info
Date/Time
Order info
Ver/Num info
00 : 00
SET
SFT
INC
▲
▼
►
►
►
Specify the Tag No..
Move cursor with [INC] and [DEC] according
to the menu path above, and select the
“Order info” then push [SET].
F0527.ai
Tag No
FT-1234
FT-1234
00 : 00
SET
SFT
INC
For Tag No., up to 8 characters can be
entered from display panel.
The switch's functionality of setting the Flow
rate span is as below:
Plus/minus and mumeric change: [INC]
Movement on digits: [SFT]
Determination of parameter: [SET]
Available characters: ASCII characters
Push [SET] to decide while the value of Tag
No. is blinking. The screen returns to the
setting page after the setting.
5.5 microSD Card Setting
For the device with optional code MC, by setting the
dedicated microSD card into the slot on the display unit,
the parameter setting can be stored into it. The
stored data can be restored to the device. For the
detailed function, read the user’s manual of applicable
communication type as listed in Table 1.1.
WARNING
Use only micro SD cards sold by YOKOGAWA.
Operation cannot be guaranteed when other cards are
used.
(1) Installing microSD Card
Carefully insert the dedicated microSD card into the slot
on the display unit until the slot holds the card. (see
Figure 5.5).
F0528.ai
microSD card
22.000mA
0.0%
0.00000
m/s
00 : 00
VEL
FLP
A01
SET
SFT
INC
Figure 5.5
microSD setting
(2) Removing microSD Card
The microSD is released from the slot by pushing it. To
prevent from losing the microSD card, be careful to
handle the card.
IMPORTANT
If the microSD card is removed without execution of
“Unmount” on parameter setting, it may result in
the corruption of stored data and the abnormal
operation of device.
Display Menu Path:
Device setup►microSD►Unmount
Basic Operating Procedures