![YASKAWA Z1000U Series Programming Manual Download Page 71](http://html2.mh-extra.com/html/yaskawa/z1000u-series/z1000u-series_programming-manual_3226538071.webp)
Setting 1: Multi-step Speed Operation Enabled
Multi-step speed inputs are still active and can override the frequency reference from the communications option even when
the NetRef command is selected.
n
F6-08: Reset Communication Parameters
Determines whether F6-
oo
/F7-
oo
communication-related parameters are reset after initialization.
No.
Parameter Name
Setting Range
Default
F6-08
Reset Communication Parameters
0, 1
0
Setting 0: Do Not Reset F6-
oo
/F7-
oo
Parameters after Initialization Using A1-03
Setting 1: Reset F6-
oo
/F7-
oo
Parameters after Initialization Using A1-03
Note:
F6-08 is not reset when the drive is initialized.
u
CC-Link Parameters
Parameters F6-04, F6-10, F6-11, and F6-14 set the drive to operate on a CC-Link network.
n
F6-04: bUS Error Detection Time
Sets the delay time for bUS error detection.
No.
Parameter Name
Setting Range
Default
F6-04
bUS Error Detection Time
0.0 to 5.0 s
2.0 s
n
F6-10: CC-Link Node Address
Sets the node address of a CC-Link option board.
No.
Parameter Name
Setting Range
Default
F6-10
CC-Link Node Address
0 to 64
0
n
F6-11: CC-Link Communication Speed
Sets the communication speed for a CC-Link option card.
No.
Parameter Name
Setting Range
Default
F6-11
CC-Link Communication Speed
0 to 4
0
Setting 0: 156 kbps
Setting 1: 625 kbps
Setting 2: 2.5 Mbps
Setting 3: 5 Mbps
Setting 4: 10 Mbps
n
F6-14: bUS Error Auto Reset
Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.
No.
Parameter Name
Setting Range
Default
F6-14
bUS Error Auto Reset
0, 1
0
Setting 0: Disabled, Auto Reset Not Possible
Setting 1: Enabled, Auto Reset Possible
u
MECHATROLINK Parameters
n
F6-20: MECHATROLINK Station Address
Sets the station address when the MECHATROLINK option is installed.
Note:
All station addresses must be unique. Setting this parameter to 20 or 3F will trigger a Station Address Error (AEr) and turn on the “ERR”
light.