Terminal V2
1.
View the value set to F4-02 (Terminal V2 Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being viewed in F4-03 will be output from terminal V2.
2.
Adjust F4-04 viewing the monitor connected to the terminal V2.
3.
View the value set to F4-06 on the digital operator, terminal V2 will output a voltage equal to 0% of the parameter
being set in F4-03.
4.
Adjust F4-06 viewing the output signal on the terminal V2.
n
F4-07, F4-08: Terminal V1, V2 Signal Level
Sets the output signal level for terminals V1 and V2.
No.
Parameter Name
Setting Range
Default
F4-07
Terminal V1 Signal Level
0, 1
0
F4-08
Terminal V2 Signal Level
0, 1
0
Setting 0: 0 to 10 V
Setting 1: -10 to 10 V
u
F5: Digital Output Card Settings
These parameters set the drive for operation with the digital output option card DO-A3. Refer to the instruction manual
packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F5-01 through F5-08: Digital Output Option Card Terminal Function Selection
When F5-09 = 2, the parameters listed in the table below assign functions to the output terminals on the option card.
No.
Name
Setting Range
Default
F5-01
Terminal P1-PC Output Selection
0 to 1B6
0: During run
F5-02
Terminal P2-PC Output Selection
0 to 1B6
1: Zero speed
F5-03
Terminal P3-PC Output Selection
0 to 1B6
2: Speed agree
F5-04
Terminal P4-PC Output Selection
0 to 1B6
4: Frequency detection 1
F5-05
Terminal P5-PC Output Selection
0 to 1B6
6: Drive ready
F5-06
Terminal P6-PC Output Selection
0 to 1B6
37: During frequency output
F5-07
Terminal M1-M2 Output Selection
0 to 1B6
F: Not used
F5-08
Terminal M3-M4 Output Selection
0 to 1B6
F: Not used
n
F5-09: DO-A3 Output Mode Selection
Determines how the DO-A3 option card works with the drive.
No.
Parameter Name
Setting Range
Default
F5-09
DO-A3 Output Mode Selection
0 to 2
0
Note:
Refer to TOBP C730600 41 Yaskawa AC Drive-Option DO-A3 Installation Manual for more details on F5-09 settings.
Setting 0: Separate Output Functions for Each of 8 Terminals
Setting 1: Binary Output
Setting 2: Output Functions Assigned by F5-01 through F5-08
u
F6 and F7: Communication Option Card
These parameters configure communication option cards and communication fault detection methods.
n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
1.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
69
1
Parameter Details