No.
Name
Setting Range
Default
b8-05
Power Detection Filter Time
0 to 2000 ms
20 ms
n
b8-06: Search Operation Voltage Limit (V/f)
Sets the voltage limit for the Speed Search optimal output voltage detection as a percentage of the maximum output voltage.
The drive will keep the output voltage above this level during the search operation to prevent motor stalling.
Note:
If set too low, the motor may stall when the load is suddenly increased. Disabled when set to 0. Setting this value to 0 does not disable
Energy Saving.
No.
Name
Setting Range
Default
b8-06
Search Operation Voltage Limit
0 to 100%
0%
1.2 b: Application
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
45
1
Parameter Details