A.16 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection. Changing the control mode initializes these
parameters to the values shown here.
u
A1-02 (Control Mode) Dependent Parameters
Table A.3 A1-02 (Control Mode) Dependent Parameters and Default Values
No.
Name
Setting Range
Resolution
Control Modes (A1-02)
V/f (0)
OLV/PM (5)
b1-24
Commercial Power Switching Selection
0, 1
–
0
0
b2-01
DC Injection Braking Start Frequency
0.0 to 10.0
0.1 Hz
0.5 Hz
0.5 Hz
b2-04
DC Injection Braking Time at Stop
0.00 to 10.00
0.01 s
0.50 s
0.00 s
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
0.00 to 6.00
–
<1>
0.3
b3-09
Current Control Integral Time during Speed Search
(Speed Estimation Type)
0.0 to 1000.0
0.0 ms
2.00 ms
4.00 ms
b3-24
Speed Search Method Selection
1, 2
–
2
2
b8-01
Energy Saving Control Selection
0, 1
–
0
–
C2-01
S-Curve Time at Acceleration Start
0.00 to 10.00
0.01 s
0.20 s
1.00 s
C4-01
Torque Compensation Gain
0.00 to 2.50
0.01
1.00
0.00
C4-02
Torque Compensation Primary Delay Time
0 to 10000
1 ms
200 ms
100 ms
C6-02
Carrier Frequency Selection
1 to 4, F
–
<1>
<1>
E1-04
Maximum Output Frequency
40.0 to 400.0
0.1 Hz
60.0
<2>
E1-05
Maximum Voltage
0.0 to 255.0
<3>
0.1 V
575
<4>
<2>
E1-06
Base Frequency
0.0 to 400.0
0.1 Hz
60.0
<2>
E1-07
Middle Output Frequency
0.0 to 400.0
0.1 Hz
3.0
–
E1-08
Middle Output Frequency Voltage
0.0 to 255.0
<3>
0.1 V
15.0
<4>
–
E1-09
Minimum Output Frequency
0.0 to 400.0
0.1 Hz
1.5
<2>
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0
<3>
0.1 V
9.0
–
L1-01
Motor Overload Protection Selection
0 to 4
–
1
4
L8-18
Software Current Limit Selection
0 to 1
–
<5>
0
L8-38
Carrier Frequency Reduction Selection
0 to 2
–
<1>
0
L8-40
Carrier Frequency Reduction Off Delay Time
0.00 to 2.00
0.01 s
0.50 s
0.00 s
<1> Default setting value is determined by parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E5-01, Motor Code Selection.
<3> Values shown are specific to 200 V class drives. Double the values for 400 V class drives.
<4> This setting value depends on rated output current and V/f pattern selection in parameter E1-03.
<5> Default setting value is determined by the drive software version.
PRG: 6113 and earlier: 0
PRG: 6114 and later: Default setting is dependent on parameter A1-02, Control Method Selection
A.16 Control Mode Dependent Parameter Default Values
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
257
A
Parameter List