A.11 n: Special Adjustment
The n parameters adjust more advanced performance characteristics such as Hunting Prevention, speed feedback detection,
High Slip Braking, and Online Tuning for motor line-to-line resistance.
u
n1: Hunting Prevention
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
n1-01
(0580)
Hunting Prevention
Selection
Hunt Prev Select
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
n1-02
(0581)
Hunting Prevention
Gain Setting
Hunt Prev Gain
If the motor vibrates while lightly loaded, increase the gain by
0.1 until vibration ceases. If the motor stalls, decrease the gain
by 0.1 until the stalling ceases.
Default: 1.00
Min.: 0.00
Max.: 2.50
n1-03
(0582)
Hunting Prevention
Time Constant
Hunt Prev Time
Sets the time constant used for Hunting Prevention.
Default:
<1>
Min.: 0 ms
Max.: 500 ms
n1-05
(0530)
Hunting Prevention
Gain while in Reverse
Hprev Gain @Rev
Sets the gain used for Hunting Prevention. If set to 0, the gain
set to n1-02 is used for operation in reverse.
Default: 0.00
Min.: 0.00
Max.: 2.50
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
u
n3: Overexcitation Braking
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
n3-13
(0531)
Overexcitation
Deceleration Gain
Hflux Brake Gain
Sets the gain applied to the V/f pattern during Overexcitation
Deceleration (L3-04 = 4).
Default: 1.10
Min.: 1.00
Max.: 2.00
u
n8: PM Motor Control Tuning
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
n8-45
(0538)
Speed Feedback
Detection Control Gain
PM Spd Fdbk Gain
OLV/PM
OLV/PM
Increase this setting if hunting occurs. Decrease to lower the
response.
Default: 0.80
Min.: 0.00
Max.: 10.00
n8-47
(053A)
Pull-In Current
Compensation Time
Constant
PM Pull-in I Tc
OLV/PM
OLV/PM
Sets the time constant to make the pull-in current reference and
actual current value agree. Decrease the value if the motor
begins to oscillate, and increase the value if it takes too long for
the current reference to equal the output current.
Default: 5.0 s
Min.: 0.0
Max.: 100.0
n8-48
(053B) Pull-In Current
PM No-load Curr
OLV/PM
OLV/PM
Defines the d-Axis current reference during no-load operation
at a constant speed. Set as a percentage of the motor rated
current. Increase this setting if hunting occurs while running at
constant speed.
Default: 30%
Min.: 20
Max.: 200
n8-49
(053C)
d-Axis Current for High
Efficiency Control
EnergySav ID Lvl
OLV/PM
OLV/PM
Sets the d-Axis current reference when running a high load at
constant speed. Set as a percentage of the motor rated current.
Default:
<1>
Min.: -200.0%
Max.: 0.0%
n8-51
(053E)
Acceleration/
Deceleration Pull-In
Current
PM Pull-in I@Acc
OLV/PM
OLV/PM
Sets the d-Axis current reference during acceleration/
deceleration as a percentage of the motor rated current. Set to a
high value when more starting torque is needed.
Default: 50%
Min.: 0
Max.: 200
n8-54
(056D)
Voltage Error
Compensation Time
Constant
PM V Error CompT
OLV/PM
OLV/PM
Adjusts the value when hunting occurs at low speed. If hunting
occurs with sudden load changes, increase n8-54 in increments
of 0.1. Reduce this setting if oscillation occurs at start.
Default: 1.00 s
Min.: 0.00
Max.: 10.00
A.11 n: Special Adjustment
234
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual