A.8 F: Option Settings
u
F2: Analog Input Card Settings (AI-A3)
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F2-01
(038F)
Analog Input Option
Card Operation
Selection
AI Function Sel
0: 3ch Individual
1: 3ch Addition
0: Option card input terminals V1, V2, and V3 replace drive
input terminals A1, A2, and A3.
1: Input signals to terminals V1, V2, and V3 are added together
to create the frequency reference.
Default: 0
Range: 0, 1
F2-02
(0368)
Analog Input Option
Card Gain
AI Input Gain
Sets the gain for the input signal to the analog card.
Default: 100.0%
Min.: -999.9
Max.: 999.9
F2-03
(0369)
Analog Input Option
Card Bias
AI Input Bias
Sets the bias for the input signal to the analog card.
Default: 0.0%
Min.: -999.9
Max.: 999.9
u
F3: Digital Input Card Settings (DI-A3)
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F3-01
(0390)
Digital Input Option
Card Input Selection
DI Function Sel
0: BCD 1%
1: BCD 0.1%
2: BCD 0.01%
3: BCD 1 Hz
4: BCD 0.1 Hz
5: BCD 0.01 Hz
6: BCD(5DG) 0.01 Hz
7: Binary
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5-digit), 0.02 Hz units
7: Binary input
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 40961/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
When the digital operator units are set to be displayed in Hz or
user-set units (o1-03 = 2 or 3), the units for F3-01 are
determined by parameter o1-03.
Default: 0
Range: 0 to 7
F3-03
(03B9)
Digital Input Option DI-
A3 Data Length
Selection
Data length Sel
0: 8bit
1: 12bit
2: 16bit
0: 8 bit
1: 12 bit
2: 16 bit
Default: 2
Range: 0 to 2
u
F4: Analog Monitor Card Settings (AO-A3)
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F4-01
(0391)
Terminal V1 Monitor
Selection
AO Ch1 Select
Sets the monitor signal for output from terminal V1. Set this
parameter to the last three digits of the desired U
o
-
oo
monitor. Some U parameters are available only in certain
control modes.
Default: 102
Range: 000 to 999
F4-02
(0392)
Terminal V1 Monitor
Gain
AO Ch1 Gain
Sets the gain for voltage output via terminal V1.
Default: 100.0%
Min.: -999.9
Max.: 999.9
F4-03
(0393)
Terminal V2 Monitor
Selection
AO Ch2 Select
Sets the monitor signal for output from terminal V2. Set this
parameter to the last three digits of the desired U
o
-
oo
monitor. Some U parameters are available only in certain
control modes.
Default: 103
Range: 000 to 999
F4-04
(0394)
Terminal V2 Monitor
Gain
AO Ch2 Gain
Sets the gain for voltage output via terminal V2.
Default: 50.0%
Min.: -999.9
Max.: 999.9
A.8 F: Option Settings
210
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual