No.
Name
Setting Range
Default
T1-07
Motor Base Speed
0 to 24000 r/min
1750 r/min
n
T1-11: Motor Iron Loss
Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron
loss that the drive automatically calculated when the motor capacity was entered to T1-02. Enter the motor iron loss value
listed to T1-11 if the motor test report is available.
No.
Name
Setting Range
Default
T1-11
Motor Iron Loss
0 to 65535 W
Determined by
E2-11
n
T1-12: T1 Tuning Start
Set T1-12 to 0 to start IM Auto-Tuning.
No.
Name
Setting Range
Default
T1-12
T1 Tuning Start
0
–
u
T2: Parameter Settings during PM Motor Auto-Tuning
The T2-
oo
parameters are used to set the Auto-Tuning input data for PM motor tuning.
n
T2-01: PM Motor Auto-Tuning Mode Selection
No.
Name
Setting Range
Default
T2-01
PM Motor Auto-Tuning Mode Selection
0 to 2; 14
0
Setting 0: PM Motor Parameter Settings
Setting 1: PM Stationary Auto-Tuning
Setting 2: PM Stationary Auto-Tuning for Stator Resistance
Setting 14: PM Rotational Auto-Tuning
n
T2-02: PM Motor Code Selection
If the drive is operating a Yaskawa PM motor from the SMRA, SSR1, or SST4 series, enter the motor code in T2-02 to
automatically set parameters T2-03 through T2-09. Use the motor nameplate or motor test report values to set parameters
T2-10 to T2-14. If the drive is operating a specialized motor or a motor designed by a manufacturer other than Yaskawa, set
T2-02 to FFFF and enter the data from the motor nameplate or the motor test report as prompted.
Only the designated PM motor codes may be entered. The PM motor codes accepted by the drive will differ depending on the
Refer to E5: PM Motor Settings on page 64
for motor codes.
No.
Name
Setting Range
Default
T2-02
PM Motor Code Selection
0000 to FFFF
Determined by o2-04
n
T2-03: PM Motor Type
Selects the type of PM motor the drive will operate.
No.
Name
Setting Range
Default
T2-03
PM Motor Type
0, 1
1
Setting 0: IPM motor
Setting 1: SPM motor
n
T2-04: PM Motor Rated Power
Specifies the motor rated power in kilowatts.
No.
Name
Setting Range
Default
T2-04
PM Motor Rated Power
0.00 to 650.00 kW
Determined by o2-04
1.12 T: Motor Tuning
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
161