![YASKAWA Z1000U Series Programming Manual Download Page 149](http://html2.mh-extra.com/html/yaskawa/z1000u-series/z1000u-series_programming-manual_3226538149.webp)
S3-13
PI2 Low Feedback
Detection Level
PI2 Feedback
(U5-18)
S3-15
PI2 High Feedback
Detection Level
On-delay
Timer
On-delay
Timer
S3-16
PI2 High Feedback
Detection Time
S3-14
PI2 Low Feedback
Detection Time
PI2 disabled
S3-17 = 0
False
True
False
True
Multi-function output
H2-
oo
= 71
PI2 Feedback Low
Multi-function output
H2-
oo
= 72
PI2 Feedback Low
+
-
+
-
Figure 1.80 PI Low Feedback Detection Level
n
S3-14: Secondary PI Low Feedback Detection Time
Sets the secondary PI low feedback detection delay time in seconds.
No.
Name
Setting Range
Default
S3-14
Secondary PI Low Feedback Detection Time
0.0 to 25.5 s
1.0 s
n
S3-15: Secondary PI High Feedback Level
Sets the secondary PI high feedback detection level.
No.
Name
Setting Range
Default
S3-15
Secondary PI High Feedback Level
0.00 to 600.00
<1>
300.0
<2>
<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.
n
S3-16: Secondary PI High Feedback Detection Time
Sets the secondary PI high feedback detection delay time in seconds.
No.
Name
Setting Range
Default
S3-16
Secondary PI High Feedback Detection Time
0.0 to 25.5 s
1.0 s
n
S3-17: Secondary PI Feedback Detection Selection
Selects when secondary PI controller low and high feedback detection is active.
No.
Name
Setting Range
Default
S3-17
Secondary PI Feedback Detection Selection
0 or 1
0
Setting 0: Secondary PI Enabled
Setting 1: Always
1.11 S: Special Parameters
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
149
1
Parameter Details