![YASKAWA Z1000U Series Programming Manual Download Page 138](http://html2.mh-extra.com/html/yaskawa/z1000u-series/z1000u-series_programming-manual_3226538138.webp)
n
o3-01: Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No.
Name
Setting Range
Default
o3-01
Copy Function Selection
0 to 3
0
Setting 0: Copy Select (No Function)
Setting 1: INV --> OP READ
Copies all parameters from the drive to the HOA keypad.
Note:
The copy protection for the HOA keypad is enabled by default. Set o3-01 to 1 to unlock copy protection.
Setting 2: OP --> INV WRITE
Copies all parameters from the HOA keypad to the drive.
Setting 3: OP<-->INV VERIFY
Compares the parameters in the drive with the parameter settings saved on the HOA keypad for matches.
n
o3-02: Copy Allowed Selection
Allows and restricts the use of the Copy function.
No.
Name
Setting Range
Default
o3-02
Copy Allowed Selection
0, 1
0
Setting 0: Disabled
Setting 1: Enabled
u
o4: Maintenance Monitor Settings
n
o4-01: Cumulative Operation Time Setting
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note:
The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also
be displayed in monitor U4-01.
No.
Name
Setting Range
Default
o4-01
Cumulative Operation Time Setting
0 to 9999 h
0 h
n
o4-02: Cumulative Operation Time Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in monitor U4-01.
No.
Name
Setting Range
Default
o4-02
Cumulative Operation Time Selection
0, 1
1
Setting 0: Power on Time
The drive logs the time it is connected to a power supply, regardless of whether the motor is running.
Setting 1: Run Time
The drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)
and when there is voltage output.
n
o4-03: Cooling Fan Operation Time Setting
Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03
also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after
replacing the cooling fan.
Note:
1.
The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. “300”
will be displayed in monitor U4-03.
2.
The cooling fan may require maintenance at an earlier date in harsher environments.
No.
Name
Setting Range
Default
o4-03
Cooling Fan Operation Time Setting
0 to 9999 h
0 h
1.10 o: Operator-Related Settings
138
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual