Z1-15: Interlock Wait Time
When an input is programmed for Interlock and the time set to this parameter is reached before the Interlock input goes active,
a fault will be declared. The default setting of 0.0 will never time out.
No.
Name
Setting Range
Default
Z1-15
Interlock Wait Time
0.0 to 300.0 s
0.0 s
Run Delay with Preset Speed Examples
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
t1
t2
t3
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)
Figure 5.56 Run Delay with Preset Speed Example: Default Setting
5.15 Z: Bypass Parameters
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual