Sequence Timer 3
Run at d1-03
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Mon
Sun
Sat
Fri
Thur
Wed
Tue
Sequence Timer 1
Run at d1-01
Sequence Timer 2
Run at d1-02 with PI control disabled
Figure 1.74 Sequence Timer Example 3
n
S2-01/S2-06/S2-11/S2-16: Sequence Timers 1 to 4 Start Time
Sets the start times for timers 1 to 4.
If the Stop Time is set to a higher value than the Start Time, the Sequence Timers will be active starting from the set Start
Time, run through midnight, and stop the following day at the set Stop Time.
Note:
Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer in drive software
versions PRG: 8551 and earlier.
No.
Name
Setting Range
Default
S2-01
Sequence Timer 1 Start Time
12:00AM to 11:59PM
12:00AM
S2-06
Sequence Timer 2 Start Time
12:00AM to 11:59PM
12:00AM
S2-11
Sequence Timer 3 Start Time
12:00AM to 11:59PM
12:00AM
S2-16
Sequence Timer 4 Start Time
12:00AM to 11:59PM
12:00AM
<1> Default is 00:00 and range is 00:00 to 24:00 when o4-20 is set to 1 (24-hour).
n
S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time
Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.
No.
Name
Setting Range
Default
S2-02
Sequence Timer 1 Stop Time
00:00 to 24:00
00:00
S2-07
Sequence Timer 2 Stop Time
00:00 to 24:00
00:00
S2-12
Sequence Timer 3 Stop Time
00:00 to 24:00
00:00
S2-17
Sequence Timer 4 Stop Time
00:00 to 24:00
00:00
1.11 S: Special Parameters
138