3.
After mounting the whole system, to protect the backplane bus connectors at the
last module you have to mount the bus cover, now. If the last module is a clamp
module, for adaptation the upper part of the bus cover is to be removed.
2.5 Wiring
CAUTION!
Consider temperature for external cables!
Cables may experience temperature increase due to system heat dissi-
pation. Thus the cabling specification must be chosen 5°C above ambient
temperature!
CAUTION!
Separate insulation areas!
The system is specified for SELV/PELV environment. Devices, which are
attached to the system must meet theses specifications. Installation and
cable routing other than SELV/PELV specification must be separated
from the system’s equipment!
2.5.1 Wiring CPU 01xC
For wiring the CPU 01xC has removable connectors. With the wiring of the connectors a
"push-in" spring-clip technique is used. This allows a quick and easy connection of your
signal and supply lines. The clamping off takes place by means of a screwdriver.
U
max
30V DC
I
max
10A
Cross section
0.08 ... 1.5mm
2
(AWG 28 ... 16)
Stripping length 10mm
Use for wiring rigid wires respectively use wire sleeves. When using stranded wires you
have to press the release button with a screwdriver during the wiring.
CPU connector
Data
VIPA System SLIO
Basics and mounting
Wiring > Wiring CPU 01xC
HB300 | CPU | 013-CCF0R00 | en | 19-30
22