10.7.4
Access to the WebVisu
Via the web server of the CPU, you have access to the device web page and the
Web-
Visu
, controlled via ports. Access to the
WebVisu
can be password-protected and
encrypted by means of SSL certificates. If you want to use SSL certificates, you must
integrate them in the
SPEED7 Studio
accordingly.
n
You can create users via
‘Webvisu Project > User administration’
, who can access
the
WebVisu
.
n
Via
‘Device properties > WebVisu Configuration’
, you can specify the port via which
the
WebVisu
should be reached and upload security certificates. This changes the
port for accessing the device web page.
–
HTTP port 8080 (default): The
WebVisu
can be accessed via the IP address of
the CPU with port number, such as
http://192.168.72.120:8080
. The device web
page can be accessed via the IP address of the CPU (port 80), such as
http://192.168.72.120
.
–
HTTP port 80: The
WebVisu
can be accessed via the IP address of the CPU,
such as
http://192.168.72.120
. The device web page can be accessed via the IP
address of the CPU and port 8080, such as
http://192.168.72.120:8080
.
–
SSL port 443 (default): The
WebVisu
can secure be accessed via the IP address
of the CPU with port number, such as
https://192.168.72.120:443
. The device
web page can be accessed via the IP address of the CPU and port 8080, such as
http://192.168.72.120:8080
.
Please note that the encryption of the communication can affect CPU
performance and therefore the response time of the entire system!
10.7.5
Status of the WebVisu
On the device web page at the tab
‘WebVisu’
via
‘Status’
you get the status of your
WebVisu
project. You can also determine the status at runtime by using the SSL partial
list xy3Eh. More can be found in the manual operation list (HB00_OPL_SP7) of your
CPU.
Status
Meaning
running
WebVisu
is active / has started-up and can be opened
loading webvisu project
Loading
WebVisu
project
shutting down
WebVisu
server shuts down
stop requested
WebVisu
STOP requested
stopped
WebVisu
server is down
webvisu feature not activated
WebVisu
not activated, memory card is not inserted
webvisu is disabled by the user
WebVisu
was disabled by the user
no webvisu project file found
No
WebVisu
project found
no hardware configuration loaded
No hardware configuration is loaded
invalid configuration
Invalid
WebVisu
configuration
internal error: filesystem
Error initializing the file system
webvisu project file too large
Error loading
WebVisu
project, project file too large
VIPA System MICRO
Configuration with VIPA SPEED7 Studio
Deployment Web visualization > Status of the WebVisu
HB400 | CPU | M13-CCF0000 | en | 18-50