5.2 Address assignment
Sub module
Input address
Access
Assignment
AI5/AO2
800
WORD
Analog input channel 0 (X6)
802
WORD
Analog input channel 1 (X6)
Sub module
Input address
Access
Assignment
DI24/DO16
136
BYTE
Digital input I+0.0 ... I+0.7 (X1)
137
BYTE
Digital input I+1.0 ... I+1.7 (X5)
Sub module
Input address
Access
Assignment
Counter
816
DINT
Channel 0: Counter value / Frequency value
820
DINT
Channel 1: Counter value / Frequency value
824
DINT
Channel 2: Counter value / Frequency value
828
DINT
Channel 3: Counter value / Frequency value
Sub module
Output address
Access
Assignment
Counter
816
DWORD
reserved
820
DWORD
reserved
824
DWORD
reserved
828
DWORD
reserved
Sub module
Output address
Access
Assignment
DI24/DO16
136
BYTE
Digital output Q+0.0 ... Q+0.7 (X2)
137
BYTE
Digital output Q+1.0 ... Q+1.3 (X6)