5.6.5.2
Count once
5.6.5.2.1 No main counting direction
n
The counter counts once starting with
load value
.
n
It is counted forward or backward.
n
The counter limits are fix set to maximum range.
n
At over- or underflow at the count limits, the counter jumps to the according other
count limit and the gate is automatically closed.
n
To restart the count process, you have to generate an edge 0-1 at the gate
5.6.6.2 ‘Gate function’ on page 111
n
With the configured
‘Gate function’
‘Interrupt count’
the counting is continued with
current
Counter value
.
n
With configured
‘Gate function’
‘Cancel count’
the counter starts with the
Load value
.
Limits
Valid range of values
Lower count limit
-2 147 483 648 (-2
31
)
Upper count limit
+2 147 483 647 (2
31
-1)
Interrupting gate control
Aborting gate control
VIPA System MICRO
Deployment I/O periphery
Counting > Counter operating modes
HB400 | CPU | M13-CCF0000 | en | 16-47
105