PBR | 920-1CA50 | Manual

HB153 | PBR | 920-1CA50 | en | 19-09

VIPA Networking Solutions

PROFIBUS MultiRepeater A5

www.vipa.com/en/service-support/manuals

Summary of Contents for VIPA PBR Series

Page 1: ...PBR 920 1CA50 Manual HB153 PBR 920 1CA50 en 19 09 VIPA Networking Solutions PROFIBUS MultiRepeater A5 www vipa com en service support manuals...

Page 2: ...920 1CA50_000_PBMR A5 4 GB 2019 VIPA GmbH Ohmstr 4 91074 Herzogenaurach Telephone 49 9132 744 0 Fax 49 9132 744 1864 Email info vipa com Internet www vipa com...

Page 3: ...annel Structure 9 2 6 Grounding System 10 2 7 Cable lengths for PROFIBUS DP 10 2 8 Cable types for PROFIBUS DP 11 2 9 Status display 12 3 Installation Instructions 13 3 1 Location 13 3 2 Position 13 3...

Page 4: ...be included for units which are not present at the customer site The exact scope of delivery is described in the respective purchase contract Hereby VIPA GmbH declares that the products and systems ar...

Page 5: ...VIPA It contains a description of the construction project implementation and usage Product Order number as of state HW PBMR A5 920 1CA50 01 The manual is targeted at users who have a background in a...

Page 6: ...out when the system has been disconnected from power Installation and hardware modifications only by properly trained per sonnel The national rules and regulations of the respective country must be s...

Page 7: ...he main bus The MultiRepeater refresh a received message on one Channel and transfer it to all the other Channels chicken foot topology n Because the PROFIBUS MultiRepeater A5 creates isolated segment...

Page 8: ...transmission speed n No limit in serial placement or cascading of MultiRepeaters n No address required n Integrated termination facilities switches n Configurable grounding system direct or capacitive...

Page 9: ...nnel n Suitable for all DP cables n Conveniently arranged networks n Easy extendable installations n On board DB9 female connector on each channel for maintenance activities n Cost Savings Because of...

Page 10: ...the 2 potentials ensuring protection of the signal against non DC disturbances If by accident on 1 channel the Direct Grounding is con nected with the Indirect Grounding the connection to the Direct...

Page 11: ...ance 135 165 Ohm 3 to 20 MHz Capacity 30 pF m Loop resistance 110 Ohm km Wire diameter 0 64 mm Wire area 0 32 mm2 The PROFIBUS MultiRepeater can handle cables based on multiple protection sheaths with...

Page 12: ...or more devices communi cating on the Main Channel 1 or more devices communi cating on the Main Channel Main ERROR No problem has been detected Problem in the cabling has been detected Main Channel P...

Page 13: ...create a more reliable protec tion against moist and dust water compartment and glands In this position it is also easier to read the status display 3 3 Mounting The PROFIBUS MultiRepeater has 4 mount...

Page 14: ...There is a grounding point that can be used To connect the power supply you need a 3 mm screwdriver If the power is switched on it can be diagnosed by the following indicators on the PCB n All the LE...

Page 15: ...the indirect cable shielding is not required when the ground clips are used If the Main Channel recognizes valid PROFIBUS messages from one or more connected devices the RX OK LED of the Main Channel...

Page 16: ...7 Termination The termination of the main channel has been set to OFF by default If the MultiRepeater is the last first device on the segment the termination must be set to ON The termination of the c...

Page 17: ...peater is locked to a certain transmission speed the baudrate switch should be set to the required value 1 Baudrate switch To set the rotary switch use a 3 mm screwdriver 0 Auto detect default 1 9 6 k...

Page 18: ...ect default or selectable with rotary switch Transmission speed switch 0 Normal repeating Auto detect default 1 9 6 kbps 2 19 2 kbps 3 45 45 kbps 4 93 75 kbps 5 187 5 kbps 6 500 kbps 7 1500 kbps 8 300...

Page 19: ...Powered according to IEC 61158 390 220 390 Ohm n All Channels default ON n Main Channel default OFF Cascading depth No limits Redundancy No Power supply specifications Nominal supply voltage 10 to 32...

Page 20: ...e of extension of PROFIBUS DP after DP V0 DP V1 devices shall comply with the following features n Device related diagnosis is replaced by status and alarms n The first three octets of the user parame...

Page 21: ...ter Active physical layer device that receives and retransmits all signals over a different port to increase the distance and number of devices for which signals can be correctly transferred for a giv...